Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual
Page 40
![background image](/manuals/579746/40/background.png)
40
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Chapter 4
Wiring Examples
Figure 17 - Two-hand Monitor
This example shows wiring and controller configuration when using the Guard
I/O module. If used in combination with the programs of a safety controller, the
wiring is Category 4 in accordance with EN 954-1 wiring requirements.
I0
I2
I1
I3
IN+
IN-
T0
T1
E1
T1
T2
T1
T3
S11
31803-M
S12
-
+
FE
Controller Configuration
Parameter Name
Configuration Setting
Safety Input 0
Safety Input 0 Channel Mode
Test Pulse from Test Output
Safety Input 0 Test Source
Test Output 0
Dual Channel Safety Input 0/1 Mode
Dual Channel Complementary
Dual Channel Safety Input 0/1 Discrepancy Time
100 ms (application dependent)
Safety Input 1
Safety Input 1 Channel Mode
Test Pulse from Test Output
Safety Input 1 Test Source
Test Output 1
Safety Input 2
Safety Input 2 Channel Mode
Test Pulse from Test Output
Safety Input 2 Test Source
Test Output 0
Dual Channel Safety Input 2/3 Mode
Dual Channel Complementary
Dual Channel Safety Input 2/3 Discrepancy Time
100 ms (application dependent)
Safety Input 3
Safety Input 3 Channel Mode
Test Pulse from Test Output
Safety Input 3 Test Source
Test Output 1
Test Output 0
Test Output 0 Mode
Pulse Test Output
Test Output 1
Test Output 1 Mode
Pulse Test Output