Dual-channel setting, Safety output fault recovery, Controlling devices – Rockwell Automation 1791ES-IB16 Guard I/O EtherNet/IP Safety Modules User Manual
Page 28: Dual-channel setting safety output fault recovery
![background image](/manuals/579746/28/background.png)
28
Rockwell Automation Publication 1791ES-UM001D-EN-P - May 2013
Chapter 2
Understand the Operation of Safety Functions
Dual-channel Setting
When the data of both channels is in the on state, and neither channel has a fault,
the outputs are turned on. The status is normal. If a fault is detected on one
channel, the safety output data and individual safety output status turn off for
both channels.
Figure 13 - Dual-channel Setting (not to scale)
Safety Output Fault Recovery
If a fault is detected, the safety outputs are switched off and remain in the off
state. The procedure for activating the safety output data again is as follows.
1. Remove the cause of the error.
2. Place the safety output (or safety outputs) into the safety state.
The safety output status turns on (fault cleared) when the output-error
latch time has elapsed. The I/O indicator (red) turns off. The output data
can now be controlled.
Controlling Devices
See the table for information about controlling devices.
ON
OFF
OUT0
Safety Output
Status 0, 1
OUT0
OUT1
OUT1
Safety Output
Status 0, 1
Fault Detection
Error
Detected
Remote
I/O
Data
Remote
I/O
Data
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Normal Operation
ATTENTION: Use appropriate devices as indicated in the Controlling
Device Requirements table. Serious injury can occur due to loss of safety
functions.