Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 82
Specifications
A–2
Publication 1771ĆUM127B-EN-P - December 2002
Vibration
IEC 60068-2-6 (Test Fc, Operating)
2g@ 10-500Hz
ESD Immunity
IEC 61000-4-2
4kV contact discharges
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1kHz sine-wave 80% AM from 30MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100% AM at 900MHz
EFT/B Immunity
IEC 61000-4-4
+1kV @ 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5
+2kV line-earth (CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6
10V rms with 1kHz sine wave 80% AM from 150kHz to 30MHz
Emissions
CISPR 11
Group 1, Class A (with appropriate enclosure)
Enclosure Type
None (open style
ConnectingCable(s)
1771ĆNC6 = 1.8m (6ft)
1771ĆNC15 = 4.6m (15ft)
Field WiringArm Wiring
Size
Insulation
Category
14-22AWG (2.5-0.25mm
2
) solid or stranded copper wire rated at
60
o
C or greater
3/64 inch (1.2mm) maximum
2
1
Keying
Between 26 and 28
Between 32 and 34
Certifications
(when product is marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CE
2
European Union 89/336/EEC EMC Directive,
compliant with:
EN 61000-6-4, Industrial Emissions
EN 50082-2, Industrial Immunity
EN 61000-6-2, Industrial Immunity
EN 61326, Meas./Control/Lab., Industrial Requirements
C-Tick
2
Australian Radiocommunications Act,compliant
with AS/NZS 2064, Industrial Emissions
1 Use this conductor category information for planningconductor routing. Refer to publication 1770Ć4.1, Industrial Automation Wiringand
GroundingGuidelines."
2 See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.