Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual
Page 79

7–3
Troubleshooting
Publication 1771ĆUM127B-EN-P - December 2002
Table 7.B
Module Status Reported in BTR Word 1
Decimal Bit
(Octal Bit)
Explanation
Word 1
Bit 00Ć05
Not used
Bit 06
Bad structure. This bit is set if there is an error in the BTW header.
Bit 07
Bad program. This bit is set if any of the module level programming
data is illegal.
Bit 08 (10)
Module fault. This bit is set if any of the programming data sent to the
module in the most recent BTW was illegal, or if one or more channels
has the bad calibration bit set.
Bits 09Ć10
(11Ć12)
Program verify. Indicates the result of verify request. 00 = verify not
requested; 10 = verify failed; 11 = verify succeeded
Bit 11 (13)
I/O reset. This bit is set whenever the I/O reset line on the backplane
is asserted.
Bit 12 (14)
RTS timeout. This bit is set if no BTR was requested of the module
within the RTS sample time.
Bit 13 (15)
Module alarm. This bit is set if there is an alarm bit set for one or more
channels. The input alarm bits are low, high alarm and rate alarm. The
output channel alarm bits are low and high clamp, and the rate limit
alarm.
Bit 14 (16)
Bad channel data. This bit is set if the module is in BCD mode and
one or more of the input data values sent in the last BTW are not a
legal BCD value.
Bit 15 (17)
Powerup bit. This bit is set until a BTW with programming data is
received by the module.
Word 2
Bit 00
CJC Underrange bit. This bit is set if the CJC temperature is below the
input channel minimum range.
Bit 01
CJC Overrange bit. This bit is set if the CJC temperature is above the
input channel maximum range.