beautypg.com

Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 59

background image

4–19

Configuring the Module

Publication 1771ĆUM127B-EN-P - December 2002

The following six words configure the first input channel of the
module. These words are repeated as necessary for each input in the
module. For example, if this is a 2 output/6 input module, words 1
through 4 would configure the module, words 5 through 16 would
configure the 2 output channels (six words each). Then six groups of
seven words each (one group for each input channel) would
configure the module’s six input channels.

Input Programming

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Channel 3 Programming

17

Low Scale Value

18

High Scale Value

19

Low Alarm Value

20

High Alarm Value

21

Alarm

enable

Rate Alarm: Scaled Units per second

22

Filter Time Constant: 0.1 second units

Alarm Deadband

23

Thermocouple Type

0

RTD Type

10 Ohm Offset: 0.01 Ohm units

Bit/Word Description of Input Configuration Words 17 through 23

Word

Decimal Bit

(Octal Bit)

Definition

Word 17

Bits 00Ć15

(00Ć17)

Low scale value for channel 3.

Word 18

Bits 00Ć15

(00Ć17)

High scale value for channel 3.

Word 19

Bits 00Ć15

(00Ć17)

Low alarm value for channel 3.

Word 20

Bits 00Ć15

(00Ć17)

High alarm value for channel 3.

Word 21

Bits 00Ć14

(00Ć16)

Rate alarm. If the channel's input changes at a rate faster than this value and

the alarm enable bit is set, the channel will indicate a rate alarm condition.

Legal values are from 0.05 to 50% of full scale per second.

Bit 15 (17)

Alarm enable bit. If set to 1, the module will report high alarm, low alarm,

underrange, overrange, and rate alarm conditions. If 0, these warnings

are suppressed.

Word 22

Bits 00Ć07

Alarm deadband. This field creates a hysteresis effect on the low and high

alarms. For an alarm condition to be removed, the input signal must go above

the low alarm limit or below the high alarm limit by an amount equal to the

specified deadband. Alarm deadband values must be less than or equal to

one half the difference of the high and low alarm values.