beautypg.com

Rockwell Automation 1771-N SERIES High Resolution Analog Module User Manual User Manual

Page 169

background image

Block Transfer Write and Block Transfer Read Configurations for 5 Output/3 Input 1771-N Series Modules

J–7

Publication 1771ĆUM127B-EN-P - December 2002

Block Transfer Read Bit/Word Descriptions for 5 Output/3 Input

Modules

Word

Decimal Bit

(Octal Bit)

Definition

Word 0

Bits 00-15

(00-17)

Constant = 8800 hexadecimal

Word 1

Bits 00-05

Not used

Word 1

Bit 06

Bad structure. This bit is set if there is an error in the BTW header.

Bit 07

Bad program. This bit is set if any of the module level programming data is

illegal.

Word 1

Bit 08 (10)

Module fault. This bit is set if any of the programming data sent to the module

in the most recent BTW was illegal, or if one or more channels has the bad

calibration bit set.

Bits 09-10

(11-12)

Program verify. Indicates the result of verify request. 00 = verify not

requested; 10 = verify failed; 11 = verify succeeded

Bit 11 (13)

I/O reset. This bit is set whenever the I/O reset line on the backplane is

asserted.

Bit 12 (14)

RTS timeout. This bit is set if a BTR was not requested of the module within

the RTS sample time.

Bit 13 (15)

Module alarm. This bit is set if there is an alarm bit set for one or more

channels. The input alarm bits are low, high alarm and rate alarm. The output

channel alarm bits are low and high clamp, and rate limit alarm.

Bit 14 (16)

Bad channel data. This bit is set if the module is in BCD mode and one or

more of the input data values sent in the last BTW are not a legal BCD value.

Bit 15 (17)

Powerup bit. This bit is set until a BTW with programming data is received by

the module.

Bit 00

Cold junction compensation (CJC) underrange bit. This bit is set if the CJC

temperature is below 0

o

C.

Word 2

Bit 01

Cold junction compensation (CJC) overrange bit. This bit is set if the CJC

temperature is above 70

o

C.

Bits 02-14

(02-16)

Not used. Always 0

Bit 15 (17)

Always = 1

Word 3

Bits 00-15

(00-17)

Cold junction temperature. Units of 0.01 degrees C or 0.1 degrees F. (0.1

degrees C or 1.0 degrees F in BCD.)