Block Transfer Write and Block Transfer Read Configurations for 5 Output/3 Input 1771-N Series Modules
J–4
Publication 1771ĆUM127B-EN-P - December 2002
Definition
Decimal Bit
(Octal Bit)
Word
Bit 00
Verify. If this bit is set to 1, the module will compare its current programming with the
programming downloaded in the BTW. If they are the same, it will verify good; if they
are different, the module will verify bad. In no case will any programming data in the
BTW be applied to the module.
Bit 01
Temperature scale. 0 = Celsius, 1 = Fahrenheit
Word 6
Bit 02
BCD select.
1 = all values in BCD format.
0 = all values in 2's complement binary
Bits 03-14
(03-16)
Not used. Always 0
Bit 15 (17)
CJ alarm enable. A value of 1 enables over and underrange indication for the cold
junction channel. If the module does not have a cold junction channel, this bit is 0.
Word 7
Bits 00-15
(00-17)
Real time sample. Sample time in milliseconds. 0 = off.
RTS minimum is 100msec (counts = 100). Maximum 10 seconds in binary; 9.999
seconds in BCD.
Word 8
Bits 00-15
(00-17)
Low scale value for channel 1. Scale values are limited to +32767 in binary format;
+7999 in BCD format.
Word 9
Bits 00-15
(00-17)
High scale value for channel 1. Scale values are limited to +32767 in binary format;
+7999 in BCD format.
Word 10
Bits 00-15
(00-17)
Low clamp value for channel 1. The channel output will not be allowed to go below
this value (in scaled units) regardless of the data sent to the module. Clamp values
are limited to +32767 in binary format; +7999 in BCD format.
Word 11
Bits 00-15
(00-17)
High clamp value for channel 1. The channel output will not be allowed to go above
this value (in scaled units) regardless of the data sent to the module. Clamp values
are limited to +32767 in binary format; +7999 in BCD format.
Bits 00-11
(00-13)
Maximum ramp rate. If this field is not 0, the module will limit the maximum rate of
change for this channel to be a percentage of the scaled range of the module. Legal
values are from 1 to 200% of full scale/second.
Bit 12 (14)
Constant = 0
Word 12
Bits 13-14
(15-16)
Reset state. This field controls what the channel will output if the I/O reset line is
asserted:
00 binary = last state;
01 binary = minimum output; (example: < -10V, < 4mA)
10 binary = maximum output; (example: > 10V, > 22mA)
11 binary = user reset value.
Bit 15 (17)
Alarm enable. If set to 1, the module reports high clamp, low clamp and rate limit. If
0, these warnings are suppressed.
Word 13
Bits 00-15
(00-17)
Reset value. If the user selects the channel to go to a user reset value upon I/O
reset, the value in scaled units is entered here. Otherwise, set to 0.
Word 14
thru 19
Same as words 8 thru 13 but for channel 2.
Word 20
thru 25
Same as words 8 thru 13 but for channel 3.
Word 26
thru 31
Same as words 8 thru 13 but for channel 4.
Word 32
thru 37
Same as words 8 thru 13 but for channel 5.
Word 38
Bits 00-15
(00-17)
Low scale value for channel 6.
Word 39
Bits 00-15
(00-17)
High scale value for channel 6.