By setting trigger “None”, the Data Logger can be stopped only by a stop command from operator panel, system or after a trip caused by the relay.

5.1.2.5

Setting the stopping delay

Stopping delay can be set within the range 0.00 [s] to 10.00 [s], by 0.01 [s] steps.

5.1.3

Recording time windows

The measurements are recorded in a time window, the duration of which is defined and synchronized by a selectable event (Trigger).

The following figure displays time window, trigger and samples available:

5/6

Restart

Stop delay

Restart

Stop event

Data logger

6/6

Stop

Restart

Stop

Stop delay

Data logger

5.1.2.4 Events and display of custom Triggers

From the system, custom Triggers can be set to match the events given in par. 5.2.

In case of custom trigger, the following page will be displayed:

User may select sampling frequency (see par. 5.1.2.2), type of Trigger event (see par. 5.1.2.3) and stopping delay (see par. 5.1.2.4) so as to obtain

a required pre-triggering over the selected event.

According to the value set, stopping delay may have a zero, lower or higher duration over recording duration, as given in the following figure:

5/5

None

Any Trip

Custom

L Prealarm

Stop event

4/6

0.00 s

Stop event

Stop delay

Sampling freq.

Data logger

Stop delay

Enter password

0.00 s

Enter ↵

In the event of a trip, this data storage process is stopped after 10 ms, even if a longer stopping delay has been selected.

5.1.2.6

Restart/Stop Data Logger

By means of the Restart/Stop options, Data Logger recording may be restarted/stopped.

Stopping delay

Recording time

Samples

Measurements available

Stopping delay = 0

Stopping delay < duration of recording

Stopping delay > duration of recording