4.2.6 Communication Module Menu
Parameter/Function
Values
Notes
Local/Remote
Local/Remote
Serial address
1 ... 247
247 default address
Baudrate
9600 bit/s
19200 bit/s
Physical protocol
8,E,1 - 8,0,1 - 8,N,2 - 8,N,1
Addressing
standard Modbus
4.3 Contact S51/MM
4.3.1 General characteristics
The contact gives feedback about "MM" protection enabled.
4.3.2 Characteristics of the signalling contacts
The following data are defined for resistive loads (cos ϕ = 1)
4.3.3 Power supply
The S51/MM signalling contact is self-powered, by auxiliary power from the relay.
Type of contact
SPST
Maximum switching voltage
130 Vdc 380 Vac
Maximum switching current
5 A
8 A
Maximum switching power
175 W
2000 VA
Breaking capacity @ 35 Vdc
5 A
——
Breaking capacity @ 120 Vdc
0.2 A
——
Breaking capacity @ 250 Vac
——
8 A
Breaking capacity @ 380 Vac
——
5.2 A
Contact/coil insulation
4000 V eff
Contact/contact insulation
1000 V eff