Rockwell Automation 140G-NTK-E12 LSIG and LSIG-MM Release User Manual
Page 21

DIR 1000587R0002 (L3821)
(21)
Select SYSTEM
press the ↵ key (enter)
Select the menu item DATE to be changed
press the ↵ key (enter)
You will be prompted to input a Password
complete password entry procedure (par. 3.3.6)
press the ↵ key (enter)
Change the date using the ↓ keys (arrow down),
↑ (arrow up) and confirm by pressing the ↵ key (enter).
Press ESC twice to return to the Main Menu.
Procedure requiring confirmation of any programming
For instance, to change the Curve of Protection L, the correct sequence is as follows:
Press ESC to access the Main Menu.
From the Main Menu, select the item PROTECTIONS
press the ↵ key (enter)
From the Protections Menu, select PROTECTION L
press the ↵ key (enter)
From the Protection L Menu, select the item CURVE
press the ↵ key (enter)
Date
Enter password
September 05,2013
Password
Enter password
0***
N
10:22:53
400 A
(I )
1
1/5
Protections settings
Measures
Settings
Protections
Menu
1/5
Protections settings
Measurements
Settings
Protections
Menu
1/15
Overload
S Protection
I Protection
L Protection
Protections
1/4
Threshold I1
Time T1
Function
L Protection
t=k/i
2
8/9
System settings
Harmonic dist.
System
Measure Store Time
Settings
1/4
January 12, 2013
Time
Language
Date
System