3.5.2 Table of error and warning messages
All messages which can be shown on the display, relating to incorrect configurations, generic alarms or deriving from protection functions, and
linked to useful information, are described below.
The following symbols in the warning signals have the following meanings:
= Warning signal/Protection in alarm mode, with no trip (trip=off)
= Protection in alarm mode, with trip on end of timing (trip=on)
= Information, no action, excepting display by relay
Alarm
message
Description
Notes
Harmonic dist.
Harmonic distortion alarm
Busbar currents with zone factor > 2.1
Contact wear
Contact wear alarm
Contact wear =100%
G (TRIP OFF)
Alarm for protection G
T Alarm
Alarm for protection T
Temperature off-range
T (TRIP OFF)
Alarm for protection T
U alarm
Protection U alarm
Protection U under timing
LC1 Load
Alarm for load control LC1
LC2 Load
Alarm for load control LC2
L1 Sensor
Alarm for L1 phase current sensor
Phase L1 sensor disconnected or faulty
L2 Sensor
Alarm for L2 phase current sensor
Phase L2 sensor disconnected or faulty
L3 Sensor
Alarm for L3 phase current sensor
Phase L3 sensor disconnected or faulty
Ne Sensor
Alarm for Ne phase current sensor
Phase Ne sensor disconnected or faulty
TC disconnected
Trip Coil disconnected or faulty
Rating Plug
Rating Plug Error absent or faulty
Phase cycle
Phase cycle inverted
Invalid date
Clock information lost
CB status
CB status error
Probable error in Q26 and/or Q27
Installation
Key plug error
CB not defined
State of circuit breaker inconsistent (Open/Closed)
Probable error in Q26 and/or Q27
Local Bus
Local Bus error
Contact wear
Contact wear prealarm
Contact wear ≥ 80%
L prealarm
Protection L prealarm
T prealarm
Protection T prealarm
Warning Iw
Iw threshold exceeded
Timing L
Timing protection L
Timing S
Timing protection S
Timing G
Timing protection G
Timing U
Timing protection U
3.5.3 Error messages displayed in pop-up window
All messages that appear on the display in a pop-up window are described below.
Error message
Description
Wrong password
Session impossible
A programming session cannot be opened due to a contingent situation (e.g. timing in progress)
Value off-range
Value beyond the established limits
Failed 1001/2001
Inconsistent thresholds of protections L and S1
Failed 1002/2002
Inconsistent thresholds of protections I and S
Failed 3001
Inconsistency as to language change
Failed 3003
Inconsistency as to external Neutral configuration
Exception 6
Control temporarily unavailable
Unavailable
Function is not available
Invalid date
Date has not been set
Parameters revised
Programming session concluded correctly
Cancelled
Programming session cancelled
Failed
Programming session rejected