DIR 1000587R0002 (L3821)

(30)

3.5.2 Table of error and warning messages
All messages which can be shown on the display, relating to incorrect configurations, generic alarms or deriving from protection functions, and

linked to useful information, are described below.

The following symbols in the warning signals have the following meanings:

= Warning signal/Protection in alarm mode, with no trip (trip=off)

= Protection in alarm mode, with trip on end of timing (trip=on)

= Information, no action, excepting display by relay

Alarm

message

Description

Notes

Harmonic dist.

Harmonic distortion alarm

Busbar currents with zone factor > 2.1

Contact wear

Contact wear alarm

Contact wear =100%

G (TRIP OFF)

Alarm for protection G

T Alarm

Alarm for protection T

Temperature off-range

T (TRIP OFF)

Alarm for protection T

U alarm

Protection U alarm

Protection U under timing

LC1 Load

Alarm for load control LC1

LC2 Load

Alarm for load control LC2

L1 Sensor

Alarm for L1 phase current sensor

Phase L1 sensor disconnected or faulty

L2 Sensor

Alarm for L2 phase current sensor

Phase L2 sensor disconnected or faulty

L3 Sensor

Alarm for L3 phase current sensor

Phase L3 sensor disconnected or faulty

Ne Sensor

Alarm for Ne phase current sensor

Phase Ne sensor disconnected or faulty

TC disconnected

Trip Coil disconnected or faulty

Rating Plug

Rating Plug Error absent or faulty

Phase cycle

Phase cycle inverted

Invalid date

Clock information lost

CB status

CB status error

Probable error in Q26 and/or Q27

Installation

Key plug error

CB not defined

State of circuit breaker inconsistent (Open/Closed)

Probable error in Q26 and/or Q27

Local Bus

Local Bus error

Contact wear

Contact wear prealarm

Contact wear ≥ 80%

L prealarm

Protection L prealarm

T prealarm

Protection T prealarm

Warning Iw

Iw threshold exceeded

Timing L

Timing protection L

Timing S

Timing protection S

Timing G

Timing protection G

Timing U

Timing protection U

3.5.3 Error messages displayed in pop-up window
All messages that appear on the display in a pop-up window are described below.

Error message

Description

Wrong password

Session impossible

A programming session cannot be opened due to a contingent situation (e.g. timing in progress)

Value off-range

Value beyond the established limits

Failed 1001/2001

Inconsistent thresholds of protections L and S1

Failed 1002/2002

Inconsistent thresholds of protections I and S

Failed 3001

Inconsistency as to language change

Failed 3003

Inconsistency as to external Neutral configuration

Exception 6

Control temporarily unavailable

Unavailable

Function is not available

Invalid date

Date has not been set

Parameters revised

Programming session concluded correctly

Cancelled

Programming session cancelled

Failed

Programming session rejected