PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Table 7 - Abbreviated Alarm Listing
Alarm
No
.
Ty
pe
(1)
(1) See the User Manual for a description of alarm types.
Description
Dig In
ConflictA
17
➁
Digital input functions are in conflict. Combinations marked with a “ ” will cause an alarm.
Dig In
ConflictB
18
➁
A digital Start input has been configured without a Stop input or other functions are in conflict.
Combinations that conflict are marked with a “ ” and will cause an alarm.
Dig In
ConflictC
19
➁
More than one physical input has been configured to the same input function. Multiple
configurations are not allowed for the following input functions.
Forward/Reverse
Run Reverse
Bus Regulation Mode B
Speed Select 1
Jog Forward
Acc2 / Dec2
Speed Select 2
Jog Reverse
Accel 2
Speed Select 3
Run
Decel 2
Run Forward
Stop Mode B
TB Man
Ref Cflct
30
➁
Occurs when:
• “Auto/Manual” is selected (default) for [Digital In3 Sel], parameter 363 and
• [TB Man Ref Sel], parameter 96 has been reprogrammed.
No other use for the selected analog input can be programmed.
Example: If [TB Man Ref Sel] is reprogrammed to “Analog In 2,” all of the factory default uses for
“Analog In 2” must be reprogrammed (such as parameters 90, 117, 128 and 179). Refer to the
Auto/Manual Examples section of the PowerFlex 700 User Manual.
To correct:
• Verify/reprogram the parameters that reference an analog input or
• Reprogram [Digital In3] to another function or “Unused.”
Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev
Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev