Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual
Page 53
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
53
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Input/Output
Connection Example
Required Parameter Changes
Analog Output
±10V, 0-20 mA Bipolar
+10V Unipolar (shown)
• Configure with Parameter 340
• Select Source Value:
Parameter 380, [Digital Out1 Sel]
• Adjust Scaling:
Parameters 343/344
2-Wire Control Non-
Reversing
(1)
24V DC internal supply
(1) Important: Programming inputs for 2 wire control deactivates all HIM Start buttons unless parameter 192, [Save HIM
Ref], bit 1 [Manual Mode] = “1.” This allows the HIM to control Start and Jog.
• Disable Digital Input:#1:
Parameter 361 = “0, Unused”
• Set Digital Input #2:
Parameter 362 = “7, Run”
• Set Direction Mode:
Parameter 190 = “0, Unipolar”
2-Wire Control
Reversing
External supply
(I/O Board dependent)
• Set Digital Input:#1:
Parameter 361 = “8, Run
Forward”
• Set Digital Input #2:
Parameter 362 = “9, Run
Reverse”
3-Wire Control
Internal supply
• No Changes Required
3-Wire Control
External supply
(I/O Board dependent).
Requires 3-wire functions
only ([Digital In1 Sel]).
Using 2-wire selections
causes a type 2 alarm.
• No Changes Required
Digital Input
PLC Output Card (Board
dependent).
• No Changes Required
Digital Output
Relays (two at terminals 14-
16) shown in powered state
with drive faulted. See page
• Select Source to Activate:
Parameters 380/384
Enable Input
• Configure with parameter 366
For dedicated hardware Enable:
Remove Jumper J10 (see page
)
+
–
24
25
26
28
Stop-Run
25
27
28
Run Rev.
Run Fwd.
115V/
+24V
Neutral/
Common
Start
24
25
26
27
28
Stop
Start
25
27
28
Stop
115V/
+24V
Neutral/
Common
25
27
28
Control from
Prog. Controller
Neutral/
Common
10k Ohm, 2 Watt
Power Source
11
12
13
14
15
16
Fault
NOT Fault
NOT Run
Run
or
32