Auxiliary Control Power Supply
If desired, an auxiliary control power supply can be used with certain drives to
keep the drive control logic up when the main AC power is removed.
An auxiliary control power supply can only be used with:
•
400/480 and 600/690 Volt drives with Vector Control (15
th
position of
the catalog number string equals “C,” or “D”).
Using an auxiliary control power supply requires the use of some type of AC line
monitoring, as well as control of the Precharge Enable signal. Consult the factory
for additional guidance.
Connection is performed at the I/O terminal block (see pages
Auxiliary Control Voltage Terminal Block Specification
ATTENTION: An Auxiliary Control Power Supply Must Not be used with any
PowerFlex 700 Standard Control drive or 200/240 Volt Vector Control drive.
Using the power supply with these drives causes equipment/component
damage.
Power supply must provide
UL Installation
300V DC, ±10%
Non UL Installation
270…600V DC, ±10%
Wire Size Range
(1)
(1) Maximum/minimum that the terminal block accepts - these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
4.0 mm
2
(12 AWG)
0.049 mm
2
(30 AWG)
0.6 N•m (5.3 lb•in)
0.6 N•m (5.3 lb•in)
PS+
PS –