Power terminal blocks, Table 4, Refer to pag es 8 through 11 for typical locations – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual
Page 33

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
33
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Typical Location - Phase Select Jumper
Table 4 - 380…480 Volt Single-Phase AC Input Ratings
Power Terminal Blocks
Refer to pages
for typical locations.
480V Single-Phase AC Input
380…400V Single-Phase AC Input
Temp.
Drive
Catalog
Number
Fr
am
e
Hp
Rating
Input
Amps
Three-Phase
Output
Drive
Catalog
Number
Fr
am
e
kW
Ratin
g
Input
Amps
Three-Phase
Output
V AC
Amps
V AC
Amps
°C
20BD292
7
125
237.4
0-460
146
20BC292
7
80
247.7
0-400
146
25
20BD325
7
125
264.3
0-460
162.5
20BC325
7
90
275.7
0-400
162.5
25
ATTENTION: National Codes and standards (NEC, VDE, BSI etc.) and local codes
outline provisions for safely installing electrical equipment. Installation must
comply with specifications regarding wire types, conductor sizes, branch circuit
protection and disconnect devices. Failure to do so can result in personal injury
and/or equipment damage.
Name
Frame
Description
Wire Size Range
see Note
(2)
(2) Maximum/minimum sizes that the terminal block accepts - these are not recommendations.
Torque
Maximum
Minimum
Maximum
Recommended
Power
Terminal Block
7
Input power, DC+,
DC–, PE, motor
connections
150.0 mm2
(300 MCM)
see Note
(3)
(3) If can be necessary to connect multiple wires in parallel to these terminals by using multiple lugs.
2.5 mm
2
(14 AWG)
2.7 N•m
(24 lb•in)
2.7 N•m
(24 lb•in)
8…10
Input power, DC+,
DC–, PE, motor
connections
300.0 mm2
(600 MCM)
see Note
2.5 mm
2
(14 AWG)
10.0 N•m
(87 lb•in)
10.0 N•m
(87 lb•in)
AUX Terminal
Block
7…10
Auxiliary Control
Voltage
PS+, PS–
(1)
(1) External control power - select drives only, see
Auxiliary Control Power Supply on page 39
for details.
4.0 mm
2
(12 AWG)
0.049 mm
2
(30 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
Fan Terminal
Block
7
User Supplied Fan
Voltage
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.9 N•m
(8.0 lb•in)
0.6 N•m
(5.3 lb•in)
8…10
4.0 mm
2
(12 AWG)
0.5 mm
2
(22 AWG)
0.6 N•m
(5.3 lb•in)
0.6 N•m
(5.3 lb•in)
LINE
TYPE
SPARE 1
SPARE 2
3-PH 1-PH
JP1
JP2
JP3
1-PH 3-PH
LINE T
YPE
3
3
3
AC Input
Precharge