Hardware Enable Circuitry (Vector Control Only)
By default, the user can program a digital input as an Enable input. The status of
this input is interpreted by drive software. If the application requires the drive to
be disabled without software interpretation, a “dedicated” hardware enable
configuration can be utilized. This is done by removing a jumper and wiring the
enable input to “Digital In 6.”
1.
Remove HIM support plate to gain access to the Main Control Board (see
pages
through
2.
Locate & remove Jumper J10 on the Main Control Board (see below).
3.
Wire Enable to “Digital In 6” (see
4.
Verify that [Digital In6 Sel], parameter 366 is set to “1, Enable.”
Hardware Enable Jumper (J10) Location
Encoder Interface Option
Encoder Terminal Designations
No.
Description
8
+12V
(1)
DC Power
(1) Jumper selectable +5/12V is available on 20B-ENC-1 Encoder Boards.
Internal power source
250 mA.
7
+12V
DC Return (Common)
6
Encoder Z (NOT)
Pulse, marker or registration input.
(2)
(2) Z channel can be used as a pulse input while A & B are used for encoder.
5
Encoder Z
4
Encoder B (NOT)
Quadrature B input.
3
Encoder B
2
Encoder A (NOT)
Single channel or quadrature A input.
1
Encoder A
8