Drive status indicators & dpi port locations, Drive status, Indicators & dpi port locations – Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual
Page 68
68
Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Drive Status Indicators & DPI Port Locations
No.
Name
Color
State
Description
➊
PWR
(Power)
Green
Steady
Illuminates when power is applied to the drive.
➋
STS
(Status)
Green
Flashing
Drive ready, but not running and no faults are present.
Steady
Drive running, no faults are present.
Yellow
Flashing, Drive Stopped
A start inhibit condition exists, the drive cannot be started.
Check parameter 214 [Start Inhibits].
Flashing, Drive Running
An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].
Steady, Drive Running
A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].
Red
Flashing
Fault has occurred. Check [Fault x Code] or Fault Queue.
Steady
A non-resettable fault has occurred.
➌
PORT
Refer to the Communication
Adapter User Manual.
Status of DPI port internal communications (if present).
MOD
Status of communications module (when installed).
NET A
Status of network (if connected).
NET B
Status of secondary network (if connected).
➍
DPI Port 1
HIM connection.
➎
DPI Port 5
Cable connection for communications adapter.
➏
DPI Port 3 or 2
Splitter cable connected to DPI Port 2 provides additional port.
➐
DPI Port 2
Cable connection for handheld and remote options. Located
on side of chassis for Frame 7 IP20, NEMA/UL Type 1.
TB11
TE
25 AMPERES RMS
MAXIMUM
PORT
NET A
NET B
MOD
➊
➋
➌
2
1or3
➍
➐
➏
➊
➋
➌
➎
Important:
Verify metal
ground tab is
bent 90° and is
under the adapter before
tightening screw. After
tightening the screw, verify
that continuity exists
between the head of the
screw and drive ground.