Rockwell Automation Publication 20B-IN014H-EN-P - June 2013

PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10

Drive Status Indicators & DPI Port Locations

No.

Name

Color

State

Description

PWR
(Power)

Green

Steady

Illuminates when power is applied to the drive.

STS
(Status)

Green

Flashing

Drive ready, but not running and no faults are present.

Steady

Drive running, no faults are present.

Yellow

Flashing, Drive Stopped

A start inhibit condition exists, the drive cannot be started.
Check parameter 214 [Start Inhibits].

Flashing, Drive Running

An intermittent type 1 alarm condition is occurring.
Check parameter 211 [Drive Alarm 1].

Steady, Drive Running

A continuous type 1 alarm condition exists.
Check parameter 211 [Drive Alarm 1].

Red

Flashing

Fault has occurred. Check [Fault x Code] or Fault Queue.

Steady

A non-resettable fault has occurred.

PORT

Refer to the Communication
Adapter User Manual.

Status of DPI port internal communications (if present).

MOD

Status of communications module (when installed).

NET A

Status of network (if connected).

NET B

Status of secondary network (if connected).

DPI Port 1

HIM connection.

DPI Port 5

Cable connection for communications adapter.

DPI Port 3 or 2

Splitter cable connected to DPI Port 2 provides additional port.

DPI Port 2

Cable connection for handheld and remote options. Located
on side of chassis for Frame 7 IP20, NEMA/UL Type 1.

TB11

TE

25 AMPERES RMS

MAXIMUM

PORT

NET A
NET B

MOD

2

1or3

Important:
Verify metal
ground tab is
bent 90° and is
under the adapter before
tightening screw. After
tightening the screw, verify
that continuity exists
between the head of the
screw and drive ground.