PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Frame 10
Fan/Blower Terminal Blocks - Frames 8…10
Fan Transformer Specifications/Fusing
Three-Phase Blower Fusing
Drive
Type
Enclosure
Rating
(120VAC)
No. of
Fans
Connect at …
DC
Input
IP00, NEMA/UL Type Open
1000 VA
2
TB9 & 10
Requires user supplied 120V AC. See page
for TB
locations and page
for terminal designations.
IP20, NEMA/UL Type 1
1000 VA
2
AC
Input
IP00, NEMA/UL Type Open
1000 VA
3
TB9, 10 & 12
Requires user supplied 120V AC. See page
for TB
locations and page
for terminal designations.
IP20, NEMA/UL Type 1
1000 VA
3
TB9, 10 & 12
A transformer (see
page
) matches the
input line voltage to
the internal fan
voltage. If line voltage
is different than the
voltage class specified
on the drive
nameplate, the
transformer taps may
require changing.
Frame
Rating
Recommended Fuses
Primary (Quantity 2)
Secondary (Quantity 1)
8 & 9
500 VA
2.8A, 600V AC, KLDR/ATQR Type
6.25A, 250V AC, Time Delay
10
1000 VA
6A, 600V AC, KLDR/ATQR Type
9A, 250V AC, Time Delay
Frame
Recommended Fuses (Quantity 3)
9
5A, 600V AC, Time Delay
Input Line Voltage
480/400V AC, 50/60 Hz
F2
H3
480
400
F3
to TB9
JMP
0
115
0
F1
H2
H1
X1
XF
X2
120V
120V
N
120V
AC Input
N
PE
PE
7
Line
Neutral
To Fan(s)
Ground
NC
R
T
S
Frame 10, AC Input, IP20 Only
120V
120V
N
120V
AC Input
N
PE
PE
7
Line
Neutral
To Fan(s)
Ground
NC
TB9, TB10
TB12
Frame 9 Only
Blower TB
Frames 8…10