Rockwell Automation 20D PowerFlex 700 Installation Instructions - Frames 7…10 User Manual
Page 51

Rockwell Automation Publication 20B-IN014H-EN-P - June 2013
51
PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
I/O Terminal Designations
No.
Signal
Fa
ct
or
y
Defa
ult
Description
Re
lat
ed
Pa
ra
m
.
1
Analog In 1 (–)
(1)
(1) Important: 0…20mA operation requires a jumper at terminals 17 & 18 (or 19 & 20). Drive damage can occur if jumper is not
installed.
(3)
(3) These inputs/outputs are dependant on a number of parameters (see “Related Parameters”).
Isolated
(4)
, bipolar, differential, ±10V/4-20mA, 11 bit & sign, 88k
ohm input impedance. For 4-20mA, a jumper must be installed at
terminals 17 & 18 (or 19 & 20).
(4) Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode
immunity.
320…
327
2
Analog In 1 (+)
3
Analog In 2 (–)
4
Analog In 2 (+)
5
Pot Common
–
For (+) and (–) 10V pot references.
6
Analog Out 1 (–)
Bipolar (current output is not bipolar), ±10V/4-20mA, 11 bit & sign,
voltage mode - limit current to 5 mA. Current mode - max. load
resistance is 400 ohms.
340…
347
7
Analog Out 1 (+)
8
Analog Out 2 (–)
9
Analog Out 2 (+)
10
HW PTC Input 1
–
1.8k ohm PTC, Internal 3.32k ohm pull-up resistor
238, 259
11
Digital Out 1 – N.C.
(2)
(2) Contacts in unpowered state. Any relay programmed as Fault or Alarm energizes (picks up) when power is applied to the drive and
deenergizes (drops out) when a fault or alarm exists. Relays selected for other functions energize only when that condition exists
and deenergize when condition is removed.
Fault
Max. Resistive Load:
240V AC/30V DC – 1200VA, 150W
Max. Current: 5A, Min. Load: 10mA
Max. Inductive Load:
240V AC/30V DC – 840VA, 105W
Max. Current: 3.5A, Min. Load: 10mA
380…
391
12
Digital Out 1 Common
13
Digital Out 1 – N.O.
NOT Fault
14
Digital Out 2 – N.C.
NOT Run
15
Digital Out 2/3 Com.
16
Digital Out 3 – N.O.
Run
17
Current In Jumper
–
Analog In 1
Placing a jumper across terminals 17 & 18 (or 19 & 20) configures that
analog input for current.
18
19
Current In Jumper
–
Analog In 2
20
21
–10V Pot Reference
–
2k ohm minimum load.
22
+10V Pot Reference
–
23
HW PTC Input 2
–
See above
24
+24VDC
–
Drive supplied logic input power.
(5)
(5) 150mA maximum Load. Not present on 115V versions.
25
Digital In Common
–
26
24V Common
–
Common for internal power supply.
27
Digital In 1
Stop - CF
115V AC, 50/60 Hz - Control & I/O Cat. No. option D
Opto isolated
Low State: less than 30V AC
High State: greater than 100V AC
24V DC - Control & I/O Cat. No. option C
Opto isolated
Low State: less than 5V DC
High State: greater than 20V DC
11.2 mA DC
361…
366
28
Digital In 2
Start
29
Digital In 3
Auto/Man.
30
Digital In 4
Speed Sel 1
31
Digital In 5
Speed Sel 2
32
Digital In 6/Hardware
Enable, see pg.
Speed Sel 3
33
Digital Out 4 – N.C.
Fault
Dedicated fault output - Not user configurable. Relay energizes (picks
up) when power is applied to the drive and deenergizes (drops out)
when a fault exists. See Terminals 11-16 for specs.
34
Digital Out 4 Common
35
Digital Out 4 – N.O.
NOT Fault
PS+
Aux. Control Power (+)
Refer to
.
PS-
Aux. Control Power (–)
Refer to
.
PE
PE Ground
PE Ground
PE
PE Ground
PE Ground
1