PowerFlex 700 Adjustable Frequency AC Drive – Frames 7…10
Common I/O Programming Changes
Your application needs may require changing parameters from their factory
default settings.
Speed Reference A
Change Speed Reference A from Analog In 2 to Analog In 1 to connect an
external potentiometer.
1.
Set Parameter 090 [Speed Ref A Sel] to option 1 “Analog In 1”
This sets the speed reference input to I/O terminals 1 & 2. For 4…20 mA
operation, a jumper must be placed between terminals 17 & 18.
2.
Set Parameter 096 [TB Man Ref Sel] to option 9 “MOP Level”
This eliminates a potential Conflict alarm condition. Analog In 2 is not a
valid Speed Reference source if selected for any of the following:
–
117 [Trim In Select]
–
126 [PI Reference Sel]
–
128 [PI Feedback Sel]
–
147 [Current Lmt Sel]
–
179 [Sleep-Wake Ref ]
3.
Set Parameter 091 [Speed Ref A Hi] to the upper value of the desired
speed reference range in Hz
4.
Set Parameter 092 [Speed Ref A Lo] to the lower value of the desired
speed reference range in Hz
Control Scheme
Change from 3 Wire Start/Stop to 2 Wire Run/Not Run at Digital In 1 &
Digital In 2.
1.
Set Parameter 361 [Digital In1 Sel] to option 7 “Run” or 9 “Run Reverse”
2.
Set Parameter 362 [Digital In2 Sel] to another option such as 8 “Run
Forward” or 10 “Jog”
See I/O Wiring Examples beginning on
.
Restoring Factory Defaults
From the Human Interface Module (HIM) Main Menu select: Memory Storage
/ Reset To Defaults
IMPORTANT
This disables the Start button on the HIM.