background image

RED

BLK

GRN

BLU

BRN

WHT

ORG

YEL

RED
BLK

GRN

BLU

BRN

WHT

ORG
YEL

POWER -

POWER +

COM

NO

NC

COM

NO

NC

600 Series

Power Supply

1581S Mini Delayed Egress

Locking Magnet

PSB560 Request-To-Exit

Touch Sense Bar

RED

BLK

WHT

BLU

RESET

BYPASS

OR

ACCESS

728U or 728UL3

Key Switch

Reset Station

RED

BLK

GRN

LED (+)

LED (+)

LED (-)

L3

OPTION

P:\INSTALLATION INST\Delayed Egress\INST-1581S\INST-1581S.vsd REV D7 03-13 Page6

System Wiring – Single Door

+

-

8 conductors

3 or 5 conductors

8 conductors

Power

Supply

To Fire Panel – Dry, Closed Contact

AC Mains

2 conductors

PUSH UNTIL ALARM

SOUNDS. DOOR CAN BE

OPENED IN 15 SECONDS.

WARNING:

APPLICATION OF VOLTAGE TO THE DRY CONTACT INPUTS OF THIS UNIT

WILL CAUSE PERMANENT DAMAGE AND VOID THE WARRANTY

To Smoke Detection System – Dry, Closed Contact

S

Smoke Detection System

Dry, Closed Contact

Patient Monitoring System

To Patient Monitoring System – Dry, Open Contact

Connection to a Infant/Patient Monitoring,

Optional Equipment and Smoke Detection

System has not been investigated by UL.