beautypg.com

84 performance data (cont) – Bryant DURAPAC 551B User Manual

Page 84

background image

84

PERFORMANCE DATA (CONT)

COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION (cont)

Do not operate at these conditions.

LEGEND

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

where hewb = enthalpy of air entering indoor coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80)

551B120 (10 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

3000/0.025

3200/0.03

4000/0.035

5000/0.04

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

146.2

134.3

122.5

111.4

147.2

135.8

124.3

113.0

147.6

138.4

129.5

123.5

153.6

143.3

136.5

130.2

SHC

42.7

60.0

76.1

93.7

43.5

61.3

79.1

97.4

47.5

68.0

89.5

109.4

49.2

75.2

100.9

123.3

kW

7.09

7.03

6.84

6.72

7.25

7.01

6.89

6.77

7.42

7.10

6.92

6.77

7.79

7.15

7.03

6.88

85

TC

139.5

127.6

115.4

104.6

140.5

128.9

118.1

107.0

132.5

121.5

116.6

137.2

128.0

122.9

SHC

35.4

51.5

68.8

87.2

36.5

53.9

72.0

91.2

61.0

82.7

102.4

68.6

93.6

115.9

kW

8.03

7.96

7.86

7.59

8.20

7.94

7.78

7.51

8.02

7.84

7.69

8.02

7.94

7.79

95

TC

133.5

120.9

108.3

97.8

121.9

111.8

101.0

126.5

113.4

109.7

131.1

119.4

115.5

SHC

29.5

43.0

61.5

80.6

46.5

64.8

84.9

53.9

75.9

95.4

62.0

86.2

108.4

kW

8.97

8.88

8.87

8.46

8.86

8.66

8.26

8.94

8.76

8.60

8.89

8.85

8.69

105

TC

112.0

99.9

90.4

113.1

103.2

93.4

117.2

105.0

100.7

122.1

110.5

105.9

SHC

36.1

54.1

73.8

38.8

57.8

78.9

45.6

68.2

86.8

53.0

78.3

99.7

kW

10.04

9.96

9.62

10.03

9.82

9.48

10.12

9.93

9.82

10.10

10.00

9.90

115

TC

103.0

91.5

83.1

104.3

94.6

85.9

107.8

96.7

91.7

113.0

101.6

96.4

SHC

29.2

46.7

66.9

31.2

50.7

72.9

37.3

60.6

78.3

44.0

70.3

90.9

kW

11.19

11.06

10.78

11.21

10.97

10.70

11.30

11.10

11.03

11.30

11.20

11.10

125

TC

94.1

83.1

75.7

95.5

86.0

78.3

98.5

88.3

82.7

104.0

92.7

86.8

SHC

22.3

39.3

60.1

23.5

43.7

66.8

29.0

52,8

69.7

35.0

62.4

82.2

kW

12.35

12.15

11.94

12.38

12.13

11.92

12.48

12.27

12.25

12.53

12.30

12.28

551B150 (12

1

/

2

TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

3750/0.08

4300/0.09

5000/0.11

6250/0.13

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

172.0

156.3

144.2

132.3

174.3

160.0

148.4

136.2

177.4

162.8

150.6

138.2

183.6

169.0

157.5

145.6

SHC

41.4

66.6

87.6

112.1

43.2

72.5

94.8

121.3

43.6

76.9

99.6

127.5

65.5

87.0

115.5

142.7

kW

9.75

9.28

8.98

8.59

9.78

9.35

9.08

8.80

9.85

9.40

9.18

8.90

9.87

9.43

9.18

8.93

85

TC

164.0

147.6

136.2

123.7

165.4

150.7

140.1

127.2

154.1

140.8

127.9

161.1

148.0

135.4

SHC

41.9

58.7

80.0

103.8

43.2

63.5

86.5

112.2

68.7

91.0

118.1

77.7

107.8

133.2

kW

10.84

10.29

9.93

9.58

11.13

10.36

10.08

9.77

10.40

10.34

10.03

10.45

10.18

9.88

95

TC

155.5

138.9

128.2

115.1

141.4

131.8

118.3

145.3

131.0

117.6

153.1

138.4

125.1

SHC

35.1

50.8

72.3

95.5

54.4

78.1

103.2

60.5

82.3

108.7

68.5

100.0

123.7

kW

12.02

11.29

10.87

10.57

11.37

11.08

10.74

11.40

11.50

11.15

11.46

11.17

10.83

105

TC

129.1

117.8

105.8

131.7

121.0

108.7

134.8

119.9

107.7

140.9

126.9

115.9

SHC

42.1

63.5

86.5

45.4

69.0

93.9

51.2

74.2

101.3

57.7

90.2

113.6

kW

12.59

12.14

11.82

12.67

12.34

11.96

12.70

12.67

12.28

12.79

12.46

12.08

115

TC

119.2

107.3

96.4

122.1

110.2

99.0

124.2

108.8

97.8

128.7

115.3

106.7

SHC

33.5

54.8

77.5

36.4

59.8

84.7

41.9

66.1

93.8

46.8

80.5

103.5

kW

13.90

13.40

13.08

13.98

13.59

13.18

14.0

13.83

13.41

14.11

13.75

13.33

125

TC

109.4

96.9

87.1

112.4

99.4

89.3

113.7

97.7

87.8

116.5

103.8

97.5

SHC

24.8

46.0

68.5

27.4

50.7

75.5

32.6

58.0

86.4

36.0

70.7

93.5

kW

15.20

14.67

14.33

15.28

14.85

14.40

15.30

15.00

14.54

15.44

15.04

14.58

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

kW

Compressor Motor Power Input

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible heat capacity (Btuh)

1.1 x cfm

tlwb = wet-bulb temperature corresponding to

enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

0

T

F

Q

0

04

-0

12

55

1B0

3

6-

15

0

This manual is related to the following products: