81

PERFORMANCE DATA (cont)

COOLING CAPACITIES, STANDARD UNITS (cont)

Do not operate at these conditions.

LEGEND

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

where h

ewb

= enthalpy of air entering indoor coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80)

551B120 (10 TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

3000/0.31

3200/0.34

4000/0.46

5000/0.61

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

152.7

140.3

129.4

115.0

153.1

141.2

130.4

118.1

154.9

145.2

134.0

122.1

158.1

147.5

136.6

125.3

SHC

46.7

65.6

82.2

97.4

47.3

66.7

84.4

101.5

49.8

71.3

93.1

113.5

51.0

77.9

103.7

124.7

kW

7.34

7.35

7.21

7.12

7.54

7.37

7.23

7.13

7.71

7.46

7.31

7.17

8.10

7.51

7.37

7.22

85

TC

150.5

137.7

125.3

110.0

151.5

138.9

126.6

113.6

142.6

130.6

117.7

144.6

133.3

122.3

SHC

44.7

65.0

81.2

95.2

44.9

66.3

83.6

99.7

71.0

92.8

112.0

76.9

103.1

122.2

kW

8.28

8.29

8.13

8.02

8.51

8.32

8.16

8.03

8.40

8.24

8.09

8.45

8.31

8.16

95

TC

147.7

133.8

120.7

103.0

135.1

121.9

107.2

138.8

125.8

112.8

141.7

128.5

118.5

SHC

43.9

63.9

79.6

92.2

65.2

82.0

97.0

70.6

91.5

109.7

76.9

102.5

118.4

kW

9.33

9.33

9.16

8.98

9.35

9.18

9.00

9.44

9.27

9.07

9.51

9.33

9.19

105

TC

128.7

115.4

96.5

129.8

116.6

99.7

133.7

120.3

107.1

136.7

122.8

114.5

SHC

62.3

77.6

89.4

63.6

80.2

93.5

69.4

89.6

106.8

76.0

100.6

114.3

kW

10.46

10.28

10.00

10.47

10.30

10.07

10.57

10.38

10.21

10.66

10.43

10.31

115

TC

123.2

109.1

90.8

124.3

110.3

92.2

127.9

114.4

100.8

130.9

116.8

110.1

SHC

60.4

75.1

86.6

61.9

77.8

90.0

67.6

87.6

100.7

74.6

98.7

109.9

kW

11.66

11.47

11.20

11.68

11.51

11.25

11.77

11.60

11.41

11.89

11.66

11.58

125

TC

117.5

101.8

86.2

118.5

103.0

87.4

121.6

107.1

96.0

124.1

110.3

104.8

SHC

58.5

72.5

84.5

60.0

75.0

87.3

65.8

85.1

96.0

72.5

96.9

104.8

kW

12.99

12.77

12.50

13.02

12.81

12.55

13.10

12.92

12.74

13.19

13.01

12.91

551B150 (12

1

/

2

TONS)

Temp (F)

Air Ent

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

3750/0.08

4300/0.09

5000/0.11

6250/0.13

Temp (F) Air Entering Evaporator — Ewb

72

67

62

72

67

62

72

67

62

72

67

62

75

TC

167.1

154.3

142.0

169.8

157.7

144.8

173.5

160.6

148.4

176.5

164.5

153.3

SHC

82.5

103.5

123.6

85.8

109.7

132.0

90.3

117.7

141.9

98.2

130.7

153.1

kW

9.44

9.18

8.95

9.50

9.26

9.01

9.60

9.33

9.07

9.68

9.43

9.17

85

TC

162.3

149.3

135.6

165.1

152.5

139.6

168.8

155.3

143.5

172.1

159.2

149.3

SHC

80.9

101.4

120.9

84.4

107.9

129.9

89.6

115.8

139.8

97.6

129.3

149.1

kW

10.49

10.18

9.97

10.55

10.27

10.02

10.67

10.32

10.11

10.75

10.43

10.21

95

TC

156.5

143.7

126.3

159.6

146.8

131.3

162.3

149.8

136.5

166.5

153.2

144.5

SHC

79.1

99.5

116.5

83.0

106.1

126.0

87.6

114.2

135.8

95.8

127.7

144.4

kW

11.60

11.30

11.01

11.69

11.39

11.10

11.75

11.47

11.20

11.87

11.56

11.35

105

TC

150.0

136.2

115.7

153.0

139.3

120.9

155.6

142.5

128.5

158.8

145.9

138.8

SHC

76.5

96.7

111.2

80.8

103.5

120.0

85.7

112.3

128.4

93.6

125.9

138.7

kW

12.76

12.42

12.09

12.83

12.52

12.20

12.91

12.62

12.32

12.96

12.72

12.52

115

TC

141.8

122.2

104.4

144.3

126.1

110.8

147.7

129.4

118.9

150.7

135.2

130.1

SHC

73.6

91.2

104.2

77.9

98.5

110.8

83.4

107.3

118.4

91.8

121.9

129.9

kW

13.85

13.55

13.22

13.94

13.64

13.35

14.05

13.73

13.50

14.14

13.86

13.70

125

TC

132.5

108.6

93.9

134.8

111.4

100.7

137.6

114.4

106.6

140.3

122.9

120.1

SHC

70.9

85.7

93.8

74.9

92.9

100.7

80.2

101.4

106.5

89.0

116.3

120.1

kW

15.04

14.66

14.44

15.14

14.75

14.55

15.23

14.85

14.72

15.29

14.94

14.84

BF

Bypass Factor

Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW

Compressor Motor Power Input

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible heat capacity (Btuh)

1.1 x cfm

t

lwb

= wet-bulb temperature corresponding to enthalpy of

air leaving indoor coil (h

lwb

)

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

0TF

Q

0

04-

01
2

5

5