ARI* CAPACITY RATINGS (cont)

ELECTRIC RESISTANCE HEATER DATA — 559F180-300

*Maximum number of stages using accessory low-ambient kit or head pressure control device and low-ambient kit.

NOTE: Heaters are rated at 240, 480, and 600 v. Use the Multiplication Factors table below to determine heater
capacity for your particular voltage.

MULTIPLICATION FACTORS

NOTE: The following equation converts kW of heat energy to Btuh: kW x 3.413 = Btuh.

EXAMPLE: 34 kW (at 230 v) heater on 208 v

= 34.0 (.751 mult factor)
= 25.5 kW capacity at 208 v.

UNIT
559F

HEATER kW

HEATER
STAGES

HEAT

PER STAGE

MAXIMUM

STAGES*

MINIMUM

HEATING CFM

Unit Voltages

208

230

460

Cfm

L/s

180

26

34

32

2

50/50

2

4500

2124

42

56

55

2

33/67

3

56

75

80

2

50/50

4

216

26

34

32

2

50/50

2

5400

2549

42

56

55

2

33/67

3

56

75

80

2

50/50

4

240

26

34

32

2

50/50

2

6000

2832

42

56

55

2

33/67

3

56

75

80

2

50/50

4

300

26

34

32

2

50/50

2

7000

3304

42

56

55

2

33/67

3

56

75

80

2

50/50

4

HEATER RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230

240

380

440

460

480

550

575

600

240

0.694

0.751

0.918

1.000

480

0.626

0.840

0.918

1.000

600

0.840

0.918

1.000