PERFORMANCE DATA (cont)

COOLING CAPACITIES, UNITS WITH PERFECT HUMIDITY™ OPTION

Do not operate at these conditions.

LEGEND

NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

where hewb = enthalpy of air entering indoor coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F db, subtract (corr factor x cfm) from SHC.
Above 80 F db, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (db – 80)

551B036 (3 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

900/0.14

1200/0.17

1500/0.20

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

44.9

41.3

37.3

34.3

46.8

43.5

39.2

35.9

48.8

45.5

41.6

38.3

SHC

12.5

17.5

22.4

26.7

13.2

19.6

25.5

31.2

13.7

21.5

28.5

35.2

kW

2.26

2.19

2.14

2.10

2.28

2.21

2.16

2.14

2.31

2.24

2.19

2.16

85

TC

42.1

38.6

34.4

31.6

44.8

41.3

37.5

33.3

47.0

43.5

38.6

35.5

SHC

10.8

15.2

20.1

25.1

11.4

17.1

23.3

29.0

12.0

18.9

26.3

32.9

kw

2.53

2.46

2.40

2.37

2.55

2.47

2.43

2.40

2.58

2.51

2.45

2.42

95

TC

39.2

35.9

31.4

28.8

44.6

39.2

35.9

30.6

47.0

41.3

35.7

32.9

SHC

9.1

13.0

17.9

23.3

14.0

14.5

21.1

26.9

14.8

16.1

24.2

30.6

kW

2.82

2.74

2.68

2.63

2.83

2.76

2.74

2.67

2.54

2.80

2.75

2.71

105

TC

37.1

33.8

29.7

27.4

36.3

32.2

28.7

38.1

32.8

30.4

SHC

7.5

10.9

15.8

21.0

12.5

18.9

24.6

14.0

21.7

28.1

kW

3.13

3.05

3.00

2.97

3.09

3.04

2.99

3.12

3.07

3.03

115

TC

31.8

28.0

25.5

33.2

28.7

26.5

34.9

30.0

27.9

SHC

9.0

13.7

18.4

10.3

16.8

22.3

11.2

19.3

25.2

kW

3.40

3.36

3.31

3.45

3.38

3.32

3.48

3.41

3.37

125

TC

28.7

26.3

23.4

29.7

25.5

22.9

31.3

27.1

25.5

SHC

6.9

12.2

17.3

7.9

14.5

20.6

9.2

17.3

22.3

kW

3.78

3.73

3.66

3.84

3.77

3.71

3.87

3.79

3.75

551B048 (4 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

1200/0.17

1450/0.19

1600/0.21

2000/0.24

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

57.5

52.9

47.5

41.5

59.4

55.7

50.9

47.5

60.5

57.0

51.7

48.1

64.1

60.5

55.6

52.1

SHC

15.9

22.7

28.4

33.4

17.6

26.1

34.1

38.9

17.2

25.9

33.7

41.6

18.7

29.4

39.1

47.5

kW

2.93

2.87

2.86

2.82

2.94

2.89

2.87

2.84

2.94

2.89

2.86

2.85

2.96

2.90

2.88

2.85

85

TC

53.1

49.2

43.8

37.1

55.2

52.1

47.2

43.6

56.4

52.9

47.9

43.7

59.5

55.4

51.4

47.0

SHC

13.8

19.8

25.5

30.4

14.8

22.2

29.5

35.8

14.9

22.5

30.9

38.8

15.7

24.2

36.0

44.3

kW

3.35

3.26

3.25

3.21

3.36

3.28

3.26

3.23

3.37

3.28

3.26

3.24

3.39

3.28

3.26

3.24

95

TC

49.0

45.8

40.1

32.8

51.0

48.2

43.6

39.4

52.3

48.8

44.0

39.3

55.2

51.7

47.4

43.0

SHC

11.7

17.2

22.5

27.3

12.2

18.4

24.8

32.6

12.5

19.0

28.1

35.9

12.8

20.7

33.0

41.0

kW

3.77

3.71

3.68

3.64

3.78

3.72

3.69

3.67

3.80

3.72

3.69

3.67

3.82

3.74

3.70

3.68

105

TC

44.4

41.6

37.0

29.7

45.7

43.2

38.9

35.4

47.1

43.9

39.7

34.7

49.3

46.5

41.4

37.5

SHC

9.0

13.5

19.5

23.9

9.6

14.7

21.7

29.2

9.8

15.1

23.9

30.7

10.0

16.4

27.8

35.1

kW

4.29

4.20

4.17

4.11

4.29

4.20

4.17

4.14

4.31

4.20

4.17

4.15

4.32

4.22

4.19

4.16

115

TC

40.0

37.2

33.2

27.1

40.6

38.4

34.0

30.8

42.1

39.4

35.5

30.0

43.8

41.3

35.2

31.9

SHC

6.5

9.9

16.4

20.7

7.2

11.3

18.5

25.6

7.0

11.2

19.7

25.4

7.4

12.4

22.4

28.6

kW

4.80

4.73

4.68

4.62

4.80

4.74

4.71

4.64

4.82

4.73

4.72

4.65

4.82

4.74

4.72

4.69

125

TC

35.1

32.4

28.1

24.9

33.8

28.1

27.4

35.3

30.5

26.6

36.1

32.0

28.7

SHC

4.8

7.2

12.9

18.3

8.4

14.5

21.9

16.8

21.1

21.2

9.5

18.3

24.1

kW

5.36

5.29

5.23

5.15

5.30

5.25

5.19

5.29

5.27

5.21

5.30

5.29

5.25

551B060 (5 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Temp (F) Air Entering Evaporator — CFM/BF

1500/0.08

1750/0.09

2000/0.11

2500/0.13

Temp (F) Air Entering Evaporator — Ewb

78

72

67

62

78

72

67

62

78

72

67

62

78

72

67

62

75

TC

79.4

69.9

62.7

56.2

85.0

74.7

67.3

61.0

90.0

78.5

71.2

64.8

81.7

75.5

69.3

SHC

21.8

29.0

36.9

43.9

23.2

31.7

40.5

51.2

24.7

34.5

44.2

55.4

37.8

52.0

62.8

kW

3.77

3.61

3.55

3.51

3.81

3.64

3.58

3.49

3.84

3.65

3.60

3.51

3.62

3.58

3.51

85

TC

75.1

65.9

59.1

51.7

70.6

63.2

56.3

75.5

66.8

60.7

78.1

70.8

65.1

SHC

18.9

25.3

34.0

41.9

27.5

37.6

48.0

30.7

41.6

52.0

33.8

47.4

58.0

kW

4.31

4.05

3.97

3.91

4.07

4.01

3.92

4.11

4.00

3.95

4.08

4.02

3.96

95

TC

75.6

61.9

55.2

47.7

66.5

58.8

51.3

70.4

61.9

55.7

74.2

65.9

60.6

SHC

24.1

21.6

31.1

40.0

23.5

34.5

44.6

26.0

38.6

47.9

30.0

42.8

52.6

kW

4.62

4.53

4.43

4.35

4.55

4.47

4.37

4.56

4.42

4.41

4.58

4.49

4.44

105

TC

57.7

51.1

44.9

61.8

54.5

47.7

65.1

57.2

50.8

68.4

60.3

56.1

SHC

18.1

27.8

35.7

20.0

31.2

40.1

22.1

34.3

43.5

26.1

38.9

48.5

kW

5.05

4.93

4.84

5.09

4.97

4.88

5.11

4.96

4.92

5.11

5.03

4.98

115

TC

53.4

47.2

42.0

56.6

50.0

44.2

59.6

52.5

46.2

62.6

54.9

51.6

SHC

14.7

24.6

31.5

16.5

27.8

35.7

18.2

30.0

39.0

22.1

34.9

44.3

kW

5.60

5.49

5.40

5.64

5.52

5.45

5.69

5.55

5.48

5.69

5.61

5.57

125

TC

48.7

42.0

36.9

51.3

45.0

39.0

54.1

46.8

40.9

56.9

49.2

45.9

SHC

10.9

19.6

28.0

12.5

22.2

31.5

13.5

24.0

34.0

16.5

28.0

38.8

kW

6.26

6.12

6.02

6.28

6.18

6.09

6.33

6.18

6.13

6.33

6.27

6.22

BF

Bypass Factor

Edb

Entering Dry Bulb

Ewb

Entering Wet Bulb

kW

Compressor Motor Power Input

SHC

Sensible Heat Capacity (1000 Btuh) Gross

TC

Total Capacity (1000 Btuh) Gross

tldb = tedb –

sensible heat capacity (Btuh)

1.1 x cfm

tlwb = wet-bulb temperature corresponding to

enthalpy of air leaving indoor coil (hlwb)

hlwb = hewb –

total capacity (Btuh)

4.5 x cfm

0

T

F

Q

0

04

-0

12

55

1B0

3

6-

15

0