GUIDE SPECIFICATIONS — SIZES 155-300 (cont)

18. Glycol Coil:

Coil shall be 2-row copper tube (

1

/

2

-in. OD) with

aluminum plate fins (590 fins/m; 15 fins/in.) and
(41.28 mm; 1.625 in. OD) copper headers. Input and
output connections shall be (41.28 mm; 1.625 in.
ODM) copper stubs for sweat connections. Coil shall
be furnished with suitable support rails, end plates,
and hardware for ready field installation in heater
compartment.

19. Alternate Drive:

Shall provide higher static drive capability to en-
hance evaporator-fan performance rpm range.

20. Hail Guard, Condenser Coil Grille:

Shall protect the condenser coil from hail, flying
debris, and damage by large objects without increas-
ing unit clearances.

21. Outdoor Air Enthalpy Sensor:

The outdoor air enthalpy sensor shall be used with
the EconoMi$er device to provide single enthalpy
control. When used in conjunction with a return air
enthalpy sensor, the EconoMi$er device will provide
different enthalpy control. The sensor allows the

EconoMi$er controller to determine if outside air is
suitable for free cooling.

22. Return Air Enthalpy Sensor:

The return air enthalpy sensor shall be used with the
EconoMi$er device. When used in conjunction with
an outdoor air enthalpy sensor, the EconoMi$er
device will provide differential enthalpy control.

23. Return Air Temperature Sensor:

The return air temperature sensor shall be used with
the EconoMi$er device. When used in conjunction
with the standard outdoor air temperature sensor,
the EconoMi$er device will provide differential tem-
perature control.

24. Light Commercial Thermidistat:

Field-installed wall-mounted thermidistat is used to
control temperature and activation of the dehumidifi-
cation package. The thermidistat can be set for
humidity settings from 50% to 90% relative humidity.