beautypg.com

158 performance data, Cooling capacities – Bryant DURAPAC 551B User Manual

Page 158

background image

158

PERFORMANCE DATA

COOLING CAPACITIES

LEGEND

NOTES:

1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:

t

lwb

= Wet-bulb temperature corresponding to enthalpy of air leaving evapo-

rator coil (h

lwb

)

Where: h

ewb

= Enthalpy of air entering evaporator coil

3. The SHC is based on 80 F edb temperature of air entering evaporator coil.

Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).

551A155 (13 TONS)

Temp (F)

Air Entering

(Edb

Evaporator Air Quantity — Cfm/BF

3600/0.03

4375/0.04

5000/0.05045

5625/0.06

6250/0.07

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

62

67

72

62

67

72

75

TC

134

145

153

137

148

156

141

149

156

144

151

157

147

152

157

SHC

111

93

72

124

103

77

130

109

77

134

114

79

137

119

79

kW

7.9

8.1

8.2

8.0

8.2

8.3

8.1

8.2

8.3

8.1

8.2

8.3

8.2

8.2

8.3

85

TC

130

140

147

133

142

149

136

144

149

139

145

150

141

146

150

SHC

109

90

68

120

97

72

127

106

73

130

110

76

132

112

76

kW

8.9

9.1

9.2

8.9

9.1

9.2

9.0

9.1

9.2

9.1

9.2

9.2

9.1

9.2

9.2

95

TC

125

134

141

128

136

142

131

138

142

133

138

142

136

139

142

SHC

106

87

66

117

94

69

122

99

71

124

104

72

127

108

73

kW

9.9

10.1

10.2

10.0

10.1

10.2

10.1

10.2

10.2

10.1

10.2

10.2

10.2

10.2

10.2

105

TC

120

129

134

123

130

134

126

131

134

128

132

135

129

132

135

SHC

104

85

63

114

91

67

117

95

67

119

100

68

120

105

70

kW

11.1

11.2

11.3

11.1

11.3

11.3

11.2

11.3

11.4

11.2

11.3

11.4

11.3

11.3

11.4

115

TC

114

122

127

117

123

127

120

124

127

121

124

127

122

125

127

SHC

100

81

60

109

87

62

111

93

64

113

95

66

114

98

66

kW

12.3

12.5

12.6

12.4

12.5

12.6

12.4

12.5

12.6

12.5

12.5

12.6

12.5

12.5

12.6

117

TC

108

115

118

122

124

127

123

124

126

123

124

127

124

125

127

SHC

98

78

57

89

77

64

91

79

64

91

80

66

92

81

66

kW

13.6

13.8

13.9

12.6

12.7

12.7

12.6

12.7

12.7

12.7

12.7

12.7

12.7

12.7

12.7

120

TC

112

119

123

114

119

123

116

120

123

117

120

123

118

120

123

SHC

100

80

59

106

85

61

108

89

62

109

92

64

110

96

64

kW

12.9

13.1

13.2

13.0

13.1

13.2

13.1

13.2

13.2

13.1

13.2

13.2

13.1

13.2

13.2

125

TC

109

115

118

111

115

119

113

116

119

114

116

119

115

116

119

SHC

98

79

57

103

84

59

105

88

61

106

90

64

107

93

63

kW

13.6

13.8

13.9

13.7

13.8

13.9

13.7

13.8

13.9

13.8

13.8

13.9

13.8

13.8

13.9

551A180 (15 TONS)

Temp (F)

Air Entering

Condenser

(Edb)

Evaporator Air Quantity — Cfm/BF

4500/0.02

5250/0.03

6000/0.04

6750/0.04

7500/0.05

Evaporator Air — Ewb (F)

62

67

72

62

67

72

62

67

72

62

67

72

62

67

72

75

TC

181

196

213

186

201

217

189

204

219

194

206

220

198

208

223

SHC

147

124

99

160

133

105

173

143

113

181

153

120

186

163

125

kW

11.2

11.6

12.0

11.3

11.7

12.1

11.4

11.8

12.1

11.6

11.9

12.2

11.7

11.9

12.2

85

TC

175

190

205

180

194

209

183

198

212

188

200

213

192

202

214

SHC

145

121

97

157

130

102

168

139

106

175

148

115

180

157

119

kW

12.3

12.7

13.1

12.5

12.8

13.2

12.6

12.9

13.3

12.7

13.0

13.3

12.8

13.1

13.4

95

TC

168

182

197

172

187

201

176

190

203

181

192

205

185

194

206

SHC

142

118

93

154

127

98

164

136

102

170

144

108

174

153

113

kW

13.5

13.9

14.3

13.6

14.0

14.4

13.8

14.1

14.5

13.9

14.2

14.6

14.0

14.3

14.6

105

TC

161

174

188

165

178

191

169

181

193

173

182

194

177

184

194

SHC

138

115

91

150

124

95

158

132

98

162

140

103

166

148

107

kW

14.8

15.2

15.6

14.9

15.3

15.7

15.1

15.4

15.7

15.2

15.5

15.8

15.3

15.5

15.8

115

TC

152

165

179

157

168

180

161

171

181

166

172

183

169

174

183

SHC

134

111

87

145

120

91

151

128

94

155

136

98

158

142

101

kW

16.1

16.5

16.9

16.2

16.6

17.0

16.4

16.7

17.0

16.6

16.8

17.1

16.7

16.9

17.1

120

TC

148

161

153

157

SHC

132

110

142

147

kW

16.8

17.2

16.9

17.1

125

TC

SHC

kW

BF

Bypass Factor

Edb — Entering Dry-Bulb
Ewb — Entering Wet-Bulb
kW

Compressor Motor Power Input

ldb

Leaving Dry-Bulb

lwb

Leaving Wet-Bulb

SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC

Total Capacity (1000 Btuh) Gross

t

ldb

= t

edb

sensible capacity (Btuh)

1.10 x cfm

h

lwb

= h

ewb

total capacity (Btuh)

4.5 x cfm

BYPASS
FACTOR

(BF)

ENTERING AIR DRY-BULB TEMP (F)

79

78

77

76

75

under 75

81

82

83

84

85

over 85

Correction Factor

.05

1.04

2.07

3.11

4.14

5.18

Use formula

shown below.

.10

.98

1.96

2.94

3.92

4.90

.20

.87

1.74

2.62

3.49

4.36

.30

.76

1.53

2.29

3.05

3.82

0TF

Q0

04-

01

2

55

1A1

55-

1

8

0

This manual is related to the following products: