Electrical installation
Control terminals
With function "Safe torque off" deactivated
l
95
EDKVF9338 DE/EN/FR 4.0
5.5.3
With function "Safe torque off" deactivated
)
Note!
If the function "Safe torque off" is not made use of, the safety relay K
SR
must
be energised permanently to ensure the tension supply of the power output
stage.
Supply via internal voltage source
ƒ
If a freely assignable digital output (e.g. X5/A1) is assigned permanently to HIGH
level, it serves as an internal voltage source. Every output has a maximum load
capacity of 50 mA.
– The relay K
SR
and two digital inputs (X5/28 and e.g. X5/E1) can be supplied with
voltage via a digital output.
– Two digital outputs must be connected in parallel and assigned permanently to
HIGH level in order to obtain the maximum wiring (relays K
SR
and X5/E1 ... X5/E5,
X5/ST1).
ƒ
For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.
GND2
+24V
+5 V
E5
A2 A3 A4 ST1ST2 59
39
3k
47k
50mA
50mA
50mA
50mA
X5 28 E1 E2 E3 E4
3k
3k
3k
3k
3k
X11 K31K32 33 34
S1
+
K
SR
A1
X3
X6
1
2
3
4
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
GND1
GND1
7
7
62 63
AIN1
AIN2
AOUTx
AOUT2
AOUT1
1
3
2
4
7
10k
10k
9300vec0137
Fig. 5−12
Wiring of digital and analog inputs/outputs with function "Safe torque off" deactivated, given an
internal voltage source
S1
Controller enable
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting: