Technical data
Rated data
Controller for a mains voltage of 400 V / 500 V
l
73
EDKVF9338 DE/EN/FR 4.0
3.3.2
Controller for a mains voltage of 400 V / 500 V
Rated data at a mains voltage of 400 V
Basis of the data
Voltage
Frequency
Supply
3/PE AC 400 V
[U
N
]
340 V − 0 % ... 577 V + 0 %
45 Hz − 0 % ... 65 Hz + 0 %
DC 565 V (alternatively)
[U
DC
]
DC 480 V − 0 % ... 800 V + 0 %
˘
Output voltage
[U
OUT
]
3 ~ 0 ... U
N
0 ... 300 Hz
9300
Mains current
1)
Typical motor power
ASM (4−pole)
Power loss
Type
I
r
[A]
P
N
[kW]
P
N
[hp]
P
V
[kW]
EVF9335−EVVxxx
2)
200
110
150
2.8
EVF9336−EVVxxx
2)
238
132
200
3.3
EVF9337−EVVxxx
2)
285
160
250
4.0
EVF9338−EVVxxx
2)
356
200
300
5.0
1)
For a controller switching frequency of 2 kHz
2)
Device in variant V210, V240, V270 or V300
9300
Output currents
Rated current
Maximum current
2)
1 kHz
1)
2 kHz
1)
4 kHz
1)
1 kHz
1)
2 kHz
1)
4 kHz
1)
Type
I
N1
[A]
I
N2
[A]
I
N4
[A]
I
M1
[A]
I
M2
[A]
I
M4
[A]
EVF9335−EVVxxx
3)
210
210
210
315
315
315
EVF9336−EVVxxx
3)
250
250
250
375
375
375
EVF9337−EVVxxx
3)
300
300
270
450
450
405
EVF9338−EVVxxx
3)
375
375
330
560
560
495
Bold print = Lenze setting
1)
Switching frequency of the inverter
2)
The currents apply to a periodic load change with an overcurrent time of 1 minute at a maximum and a base load
time of 2 minutes with maximally 75 % I
Nx
3)