Controller mains connection for a mains voltage of 400 V
l
82
EDKVF9338 DE/EN/FR 4.0
5.2
Controller mains connection for a mains voltage of 400 V
(
Stop!
The user is responsible for sufficient strain relief!
BR2
BR1
PE U
V
W
L1 L2 L3 PE
L1, L2,
L3
25-30 Nm
M8
221-264 lb-in
PE
15-20 Nm
M6
133-176 lb-in
40 mm
9300VEC003
Fig. 5−2
Mains connection example
BR1, BR2
Brake resistors can only be operated with variants V060 and V110
For connection see the 9300 vector System Manual
Fuses and cable cross−sections for the mains supply
Type
Installation to EN 60204−1
Fuse
2)
L1, L2, L3 [mm
2
]
PE [mm
2
]
EVF9335−EV
EVF9335−EVV030
EVF9335−EVV060
EVF9335−EVV110
250 A
150
2 × 50
1)
95
EVF9336−EV
EVF9336−EVV030
EVF9336−EVV060
EVF9336−EVV110
315A
150
2 × 50
1)
95
EVF9337−EV
EVF9337−EVV030
EVF9337−EVV060
EVF9337−EVV110
315A
150
2 × 50
1)
95
EVF9338−EV
EVF9338−EVV030
EVF9338−EVV060
EVF9338−EVV110
400 A
240
2 × 95
1)
150
1)
Multiple conductor; both conductors must have the same cross−section
2)
Lenze recommends to use fuses of the gRL utilisation category
Observe the national and regional legislation