INTERBUS: Invalid initialisation [0x00c88127]

INTERBUS: Data exchange stopped [0x00c88131]

INTERBUS: Received process data length is contradictory [0x00c88211]

INTERBUS: Process data length to be sent is contradictory [0x00c88212]

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The INTERBUS initialisation has failed.

Execute renewed initialisation by the master.

Response (Lenze setting printed in bold)

Setting:

C13880/1

/

C14880/1

None  System fault  Fault  Trouble  Quick stop by trouble Warning locked  Warning  Information

Cause

Remedy

Data exchange via INTERBUS has been stopped.

• Check cables and terminals.

• Execute renewed initialisation by the master.

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The number of received I/O data via INTERBUS (display in

C13860/2

/

C14860/2

) does not correspond to the

number configured by the device through port mapping

(display in

C13854/1

/

C14854/1

).

The data word sum (process data word + parameter data

words) has to consist of 1 ... 10 words (16 bits/word).

Check whether the differing data length is sufficient for

the application.

If required, adapt the port mapping or the I/O data

length of the received data.

Configuring process data (PDO mapping) ( 37)

Setting the number of process data words ( 31)

Response (Lenze setting printed in bold)

Setting: not possible

None  System error  Error  Fault  Quick stop by trouble  Warning locked  Warning  Information

Cause

Remedy

The number of I/O data to be sent via INTERBUS (display

in

C13860/2

/

C14860/2

) does not correspond to the

number configured by the device through port mapping

(display in

C13855/1

/

C14855/1

).

The data word sum (process data word + parameter data

words) has to consist of 1 ... 10 words (16 bits/word).

Check whether the differing data length is sufficient for

the application.

If required, adapt the port mapping or the I/O data

length of the data to be sent.

Configuring process data (PDO mapping) ( 37)

Setting the number of process data words ( 31)