4 protective insulation, Protective insulation, 4technical data – Lenze E94AYCIB User Manual
Page 17

Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
17
4
Technical data
4.4
Protective insulation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
4.4
Protective insulation
Danger!
Dangerous voltage
If the Servo Drives 9400 are operated on a phase earthed mains with a rated mains
voltage 400 V, external measures need to be implemented in order to ensure
protection against accidental contact.
Possible consequences:
Death or severe injuries
Protective measures:
If protection against accidental contact is required for the control terminals of the
inverter and the connections of the plugged device modules, ...
• a double isolating distance must exist.
• the components to be connected must be provided with the second isolating
distance.
Note!
The protective insulation provided in Servo Drives 9400 is implemented in accordance
with EN 61800-5-1.