4 read/write, 5 get-od, Read/write – Lenze E94AYCIB User Manual
Page 42: Get-od, 9parameter data transfer

9
Parameter data transfer
9.3
Supported PMS services
42
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
9.3.4
Read/Write
The "Read" PMS service reads parameters from the inverter. The inverter outputs the requested
parameter or an error message.
The "Write" PMS service writes on parameters of the inverter. The inverter outputs a positive
feedback or an error message.
The following error messages can occur:
9.3.5
Get-OD
The "Get-OD" PMS service reads out the object description for every parameter and data type.
Error Class
Error code
Additional
Code
[hex]
Description
6
3
0x00
No access authorisation
6
5
0x10
Impermissible job parameter
6
5
0x11
Invalid subindex
6
5
0x12
Data length too large
6
5
0x13
Data length too small
6
6
0x00
Object is no parameter
6
7
0x00
Object does not exist
6
8
0x00
Data types do not comply with each other
8
0
0x00
Request cannot be executed
8
0
0x20
Request cannot be executed at the moment
8
0
0x21
Cannot be executed because of local control
8
0
0x22
Cannot be executed because of device state
8
0
0x30
Quit value range / parameter can only be changed when the
controller is inhibited.
8
0
0x31
Parameter value too high
8
0
0x32
Parameter value too low
8
0
0x33
Sub parameter outside the value range
8
0
0x34
Value of the subparameter is too high
8
0
0x35
Value of the subparameter is too low
8
0
0x36
Maximum value is lower than minimum value
8
0
0x41
Communication object cannot be displayed on process data
8
0
0x42
Length of the process data exceeded
8
0
0x43
General collision with other values