Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
31
6
Commissioning
6.2
Possible settings via DIP switch
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.1
Setting the number of process data words
• The number of process data words can be set via the switches 1 ... 4.
• 0 ... 10 process data words can be used.
• The current setting is displayed in the »Engineer« in
/
.
Note!
The data word sum (process data word + parameter data words) has to consist of 1 ... 10
words (16 bits/word).
Impermissible settings are reported by the BE LED (red blinking).
The communication module then operates internally with the following values:
• 2 process data words (PD)
• 1 parameter data word (PCP)
DIP switch
Number of
PD
Switch
Max. number
of PCP
1
2
3
4
0
OFF
OFF
OFF
OFF
4
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
2
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
1
10
ON
OFF
ON
OFF
0
12345678
ON
OFF