Commissioning
6.2
Possible settings via DIP switch
30
Lenze · E94AYCIB communication module (INTERBUS) · Communication Manual · DMS 4.0 EN · 02/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2
Possible settings via DIP switch
[6-1]
DIP switch
E94YCIB001D
The following can be set via the S205 DIP switch:
• Number of the process data words
switches: 1 ... 4
• Number of the parameter data words
switches: 5 and 6
• Baud rate
switch: 8
Lenze setting: All switches "OFF"
Switch 7 has no function.
Note!
• All DIP switches = "OFF" (Lenze setting):
At switch-on, the configuration from the codes gets active (
).
• At least one DIP switch = "ON":
At switch-on, the values are accepted from the switch positions.
• The data word sum (process data words + parameter data words) has to consist of
1 ... 10 words (16 bits/word).
• Switch off the voltage supply of the communication module and afterwards on again
to activate changed settings.