A.1
Permissable Cable Lengths
The table herein lists the permissable cable lengths for use with an SMV inverter with an internal EMC filter.
NOTE
This table is intended as a reference guideline only; application results may vary. The values in this
table are based on testing with commonly available low-capacitance shielded cable and commonly
available AC induction motors. Testing is conducted at worst case speeds and loads.
Maximum Permissible Cable Lengths (Meters) for SMV Model with Internal EMC Filters
Mains
Model
4 kHz Carrier
(P166 = 0)
6 kHz Carrier
(P166 = 1)
8 kHz Carrier
(P166 = 2)
10 kHz Carrier
(P166 = 3)
Class A
Class B
Class A
Class B
Class A
Class B
Class A
Class B
240 V, 1-phase
(2/PE)
ESV251GG2SFG
38
12
35
10
33
5
30
N/A
ESV371GG2SFG
38
12
35
10
33
5
30
N/A
ESV751GG2SFG
38
12
35
10
33
5
30
N/A
ESV112GG2SFG
38
12
35
10
33
5
30
N/A
ESV152GG2SFG
38
12
35
10
33
5
30
N/A
ESV222GG2SFG
38
12
35
10
33
5
30
N/A
400/480 V,3-phase
(3/PE)
ESV371GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV751GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV112GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV152GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV222GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV302GG4TFG
30
4
25
2
20
N/A
10
N/A
ESV402GG4TFG
54
5
48
3
42
2
N/A
N/A
ESV552GG4TFG
54
5
48
3
42
2
N/A
N/A
ESV752GG4TFG
54
5
48
3
42
2
N/A
N/A
NOTE: The “
GG
” and
“
G
” symbols are place holders in the Model part number that contain different information depending on
the specific configuration of the model. Refer to the SMV Type Number Designation table in section 2.2 for more information.