Installation 3 installation, 1 dimensions and mounting – Lenze ESV SMV frequency inverter User Manual
Page 14

12
Lenze SMVector 13465100 EDBSV01 EN v18
Installation
3
Installation
3.1
Dimensions and Mounting
WARNING!
Drives must not be installed where subjected to adverse environmental conditions such as: combustible, oily, or
hazardous vapors; corrosive chemicals; excessive dust, moisture or vibration; direct sunlight or extreme temperatures.
3.1.1
NEMA 1 (IP31) Models < 30HP (22kW)
b2
b1
b
a
a1
c
s1
s1
s2
s2
Mounting Screws
4 x #10
18 lb-in
4 x M5
20 Nm
(
)
Type
a
in (mm)
a1
in (mm)
b
in (mm)
b1
in (mm)
b2
in (mm)
c
in (mm)
s1
in (mm)
s2
in (mm)
m
lb (kg)
G1
ESV251~~~~~B; ESV371~~~~~B
ESV751~~~~~B
3.90 (99)
3.12 (79)
7.48 (190)
7.00 (178)
0.24 (6)
4.35 (111)
0.6 (15)
2.0 (50)
2.0 (0.9)
G2
ESV112~~~~~B; ESV152~~~~~B
ESV222~~~~~B
3.90 (99)
3.12 (79)
7.52 (191)
7.00 (178)
0.26 (7)
5.45 (138)
0.6 (15)
2.0 (50)
2.8 (1.3)
G3 ESV402~~~~~B
3.90 (99)
3.12 (79)
7.52 (191)
7.00 (178)
0.30 (8)
5.80 (147)
0.6 (15)
2.0 (50)
3.2 (1.5)
H1 ESV552~~~~~B; ESV752~~~~~B 5.12 (130)
4.25 (108)
9.83 (250)
9.30 (236)
0.26 (7)
6.30 (160)
0.6 (15)
2.0 (50)
6.0 (2.0)
J1
ESV113~~~~~B; ESV153~~~~~B
ESV183~~~~~B; ESV223~~~~~B
6.92 (176)
5.75 (146)
12.50 (318) 11.88 (302)
0.31 (8)
8.09 (205)
0.6 (15)
2.0 (50)
13.55 (6.15)
Conduit Hole Dimensions
Type
N
in (mm)
P
in (mm)
P1
in (mm)
Q
in (mm)
S
in (mm)
Q
N
Q
P
S
P1
G1
1.84 (47)
1.93 (49)
.70 (18)
1.00 (25)
.88 (22)
G2
1.84 (47)
3.03 (77)
.70 (18)
1.00 (25)
.88 (22)
G3
1.84 (47)
3.38 (86)
.70 (18)
1.00 (25)
.88 (22)
H1
2.46 (62)
3.55 (90)
.13 (3)
1.38 (35)
1.13 (29)
.88 (22)
J1
3.32 (84)
4.62 (117)
.73 (19)
1.40 (36)
1.31 (33)
.88 (22)