Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 31

Lenze SMVector 13465100 EDBSV01 EN v18
29
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P110
Start Method
0
0 Normal
1 Start on Power-up
Drive will automatically start when power is
applied.
2 Start with DC Brake
When start command is applied, drive will apply
DC braking according to P174, P175 prior to
starting the motor
3 Auto Restart
Drive will automatically restart after faults, or when
power is applied.
4 Auto Restart with DC Brake
Combines settings 2 and 3
5 Flying Start/Restart - Type 1
• Drive will automatically restart after faults, or
when power is applied.
• After 3 failed attempts, drive will Auto Restart
with DC brake.
• P110 = 5, 7: Performs speed search, starting
at Max Frequency (P103)
• P110 = 6, 8: Performs speed search, starting
at the last output frequency prior to faulting
or power loss
• If P111 = 0, a flying START is performed when
a start command is applied.
• P110 = 7,8: Utilizes P280/281 to set Max
Current Level and Decel Time for restart
6 Flying Start/Restart - Type 1
7 Flying Start /Restart - Type 2
for 2-pole motors requiring a flying
restart
8 Flying Start/Restart - Type 2
for 2-pole motors requiring a flying
restart
NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up; F.UF
fault will occur if start command is applied too soon.
• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal strip
and the start command must be present.
• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays LC
(fault lockout) and requires manual reset.
• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into F.rF fault.
• P110 = 5, 6: If drive trips into F.OF fault, try P110 = 7 or 8.
WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting should
only be used on equipment that is inaccessible to personnel.
P111
Stop Method
0
0 Coast
Drive’s output will shut off immediately upon a stop
command, allowing the motor to coast to a stop
1 Coast with DC Brake
The drive’s output will shut off and then the DC
Brake will activate (refer to P174, P175)
2 Ramp
The drive will ramp the motor to a stop according
to P105 or P126.
3 Ramp with DC Brake
The drive will ramp the motor to 0 Hz and then
the DC Brake will activate (refer to P174, P175)
P112
Rotation
0
0 Forward Only
If PID mode is enabled, reverse direction is disabled
(except for Jog).
1 Forward and Reverse