Commissioning

Code

Possible Settings

IMPORTANT

No.

Name

Default Selection

P110

Start Method

0

0 Normal
1 Start on Power-up

Drive will automatically start when power is
applied.

2 Start with DC Brake

When start command is applied, drive will apply
DC braking according to P174, P175 prior to
starting the motor

3 Auto Restart

Drive will automatically restart after faults, or when
power is applied.

4 Auto Restart with DC Brake

Combines settings 2 and 3

5 Flying Start/Restart - Type 1

• Drive will automatically restart after faults, or

when power is applied.

• After 3 failed attempts, drive will Auto Restart

with DC brake.

• P110 = 5, 7: Performs speed search, starting

at Max Frequency (P103)

• P110 = 6, 8: Performs speed search, starting

at the last output frequency prior to faulting
or power loss

• If P111 = 0, a flying START is performed when

a start command is applied.

• P110 = 7,8: Utilizes P280/281 to set Max

Current Level and Decel Time for restart

6 Flying Start/Restart - Type 1

7 Flying Start /Restart - Type 2

for 2-pole motors requiring a flying
restart

8 Flying Start/Restart - Type 2

for 2-pole motors requiring a flying
restart

NOTE
• P110 = 0, 2: Start command must be applied at least 2 seconds after power-up; F.UF

fault will occur if start command is applied too soon.

• P110 = 1, 3…6: For automatic start/restart, the start source must be the terminal strip

and the start command must be present.

• P110 = 2, 4…6: If P175=999.9, dc braking will be applied for 15s.
• P110 = 3…6: Drive will attempt 5 restarts; if all restart attempts fail, drive displays LC

(fault lockout) and requires manual reset.

• P110 = 5, 6: If drive cannot catch the spinning motor, drive will trip into F.rF fault.

• P110 = 5, 6: If drive trips into F.OF fault, try P110 = 7 or 8.

WARNING!
Automatic starting/restarting may cause damage to equipment and/or injury to personnel! Automatic starting/restarting should
only be used on equipment that is inaccessible to personnel.

P111

Stop Method

0

0 Coast

Drive’s output will shut off immediately upon a stop
command, allowing the motor to coast to a stop

1 Coast with DC Brake

The drive’s output will shut off and then the DC
Brake will activate (refer to P174, P175)

2 Ramp

The drive will ramp the motor to a stop according
to P105 or P126.

3 Ramp with DC Brake

The drive will ramp the motor to 0 Hz and then
the DC Brake will activate (refer to P174, P175)

P112

Rotation

0

0 Forward Only

If PID mode is enabled, reverse direction is disabled
(except for Jog).

1 Forward and Reverse