Commissioning, 2 i/o setup parameters – Lenze ESV SMV frequency inverter User Manual
Page 33

Lenze SMVector 13465100 EDBSV01 EN v18
31
Commissioning
4.5.2
I/O Setup Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p120
Assertion Level
2
1 Low
P120 and the Assertion Level switch must both
match the desired assertion level unless P100,
P121…P124 are all set to 0. Otherwise an F.AL
fault will occur.
2 High
P121
p122
p123
p124
TB-13A Digital Input
TB-13B Digital Input
(Priority > TB13A)
Same as TB13A except:
3 = Preset #2
23 = Seq Seg, #2
TB-13C Digital Input
(Priority > TB13B, A)
Same as TB13A except:
3 = Preset #3
23 = Seq Seg, #4
TB-13D* Digital Input
(Priority > TB13C, B, A)
Same as TB13A except:
3 = Preset #4
23 = Seq Seg, #8
0
0 None
Disables input
1 AUTO Reference: 0-10 VDC
For frequency mode, see P160...P161,
For PID mode, see P204…P205,
For vector torque mode, see P330
2 AUTO Reference: 4-20 mA
3 AUTO Reference: Preset #1
* 13D: 3 = Reserved
For frequency mode see P131...P137,
For PID mode, see P231…P233,
For torque mode see, P331…P333
4 AUTO Reference: MOP Up
• Normally open: Close input to increase or
decrease speed, PID or torque setpoint.
• MOP Up is not active while in STOP
5 AUTO Reference: MOP Down
6 AUTO Reference: Keypad
7 AUTO Reference: Network
8 Control Select
Use when P100 = 4, 5 to switch between terminal
strip control and local or remote keypad control.
9 Network Enable
Required to start the drive through the network.
10 Reverse Rotation
Open = Forward Closed = Reverse
11 Start Forward
Refer to Note for typical circuit
12 Start Reverse
13 Run Forward
Refer to Note for typical circuit
14 Run Reverse
15 Jog Forward
Jog Forward speed = P134
16 Jog Reverse
Jog Reverse speed = P135
Active even if P112 = 0
17 Accel/Decel #2
Refer to P125, P126
18 DC Brake
Refer to P174; close input to override P175
19 Auxiliary Ramp to Stop
Normally closed: Opening input will ramp drive
to STOP according to P127, even if P111 is set
to Coast (0 or 1).
20 Clear Fault
Close to reset fault
21 External Fault F.EF
Normally closed circuit; open to trip
22 Inverse External Fault F.EF
Normally open circuit; close to trip
23 AUTO Ref: Sequence Segment #1
Works in Speed Mode only
24 Start Sequence
25 Step Sequence
Transition from non-asserted to asserted state
26 Suspend Sequence
WARNING
Jog overrides all STOP commands! To stop the drive while in Jog mode, the Jog input must be deactivated or a
fault condition induced.
WARNING
If the input defined to “Start Sequence” is opened during a sequence, the drive will exit sequencer mode and will run
at the specified standard or alternate speed source (dependent on drive configuration).
NOTE: P124 is
applicable to SMV
15HP (11kW) and
higher models only