Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 48

46
Lenze SMVector 13465100 EDBSV01 EN v18
Commissioning
4.5.8
Onboard Communications Parameters 15-60HP (11-45kW)
The P6xx Onboard Communication parameters are applicable to the 15HP (11kW) and higher models only.
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p600
Network Enable
0
0 Disabled
This parameter enables the onboard network
communications.
1 Remote Keypad
2 Modbus
7 Lecom
NOTE: Onboard Communications will be
disabled if:
- P600 = 0, or
- P600 = 1 and P400 = 1, or
- P600 = 2 and P400 = 2, 3, 4, 5, 6 or 7
- P600 = 7 and P400 = 2, 3, 4, 5, 6 or 7
If the onboard communications are disabled,
the user will not have access to any of the other
P6xx parameters.
P610
Network Address
1
1 - 247
Modbus
1
1 - 99
Lecom
P611
Network Baud Rate
2
0 2400 bps
2 9600 bps
Modbus
1 4800 bps
3 19200 bps
0
0 9600 bps
Lecom
1 4800 bps
2 2400 bps
3 1200 bps
4 19200 bps
P612
Network Data Format
0
0 8, N, 2
Modbus Only
1 8, N, 1
2 8, E, 1
3 8, O, 1
P620
Network Control
Level
0
0 Monitor Only
Lecom Only
1 Parameter Programming
2 Programming and Setpoint Control
3 Full Control
P624
Network Powerup
Start Status
0
0 Quick Stop
Lecom Only
1 Controller Inhibit
p625
Network Timeout
10.0
0.0 - 300.0 seconds
Modbus
50
0 - 65000 milliseconds
Lecom
P626
Network Timeout
Action
4
0 No action
Modbus
1 Stop (P111)
2 Quick Stop
3 Controller Inhibit
4 Trip Fault, F.nF1
0
0 No action
Lecom
1 Controller Inhibit
2 Quick Stop
3 Trip Fault, F.nF1
P627
Network Messages
Received
Read-Only: 0 - 9999
Valid network messages received
NOTE: When the number of messages exceeds 9999, the counter resets and resumes
counting from 0.