Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 55

Lenze SMVector 13465100 EDBSV01 EN v18
53
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
Segment #15
P780
Segment #15
Frequency Setpoint
0.0
-500.0 {Hz} 500.0
If P112 = 1, negative sign forces reverse
direction
P781
Segment #15
Accel/Decel Time
20.0
0.0
{sec} 3600.0
P782
Segment #15
Time in current step
0.0
0
0.0
{P708} 6553.5
0
{P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P783
Segment #15
Digital Output State
0
Value set in P783
0 1 2 3 4 5 6 7
Relay (Bit 0)
0 1 0 1 0 1 0 1
TB14 (Bit 1)
0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P784
Segment #15 TB30
Analog Output
Value
0.00
0.00
{VDC} 10.00
TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #16
P785
Segment #16
Frequency Setpoint
0.0
-500.0 {Hz} 500.0
If P112 = 1, negative sign forces reverse
direction
P786
Segment #16
Accel/Decel Time
20.0
0.0
{sec} 3600.0
P787
Segment #16
Time in current step
0.0
0
0.0
{P708} 6553.5
0
{P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
P788
Segment #16
Digital Output State
0
Value set in P788
0 1 2 3 4 5 6 7
Relay (Bit 0)
0 1 0 1 0 1 0 1
TB14 (Bit 1)
0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27
P789
Segment #16 TB30
Analog Output
Value
0.00
0.00
{VDC} 10.00
TB30 configuration parameter must be set to
accept this value: P150 = 10
End Segment
P790
End Segment:
Frequency Setpoint
0.0
-500.0 {Hz} 500.0
If P112 = 1, negative sign forces reverse
direction
P791
End Segment:
Accel/Decel Time
5.0
0.0
{sec} 3600.0
P792
End Segment: Delay
before P793, 794 &
795 activation
0.0
{P708} 6553.5
0
{P708} 65535
Scaling/units depend on P708
P793
End Segment:
Digital Output State
Value set in P793
0 1 2 3 4 5 6 7
Relay (Bit 0)
0 1 0 1 0 1 0 1
TB14 (Bit 1)
0 0 1 1 0 0 1 1
I/O option Relay (Bit 2)
0 0 0 0 1 1 1 1
NOTE: P441 is the Relay Output (TB-19, 20, 21) of the
optional Digital I/O module (ESVZAL0, ESVZAL1).
bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must be
set to accept data from the sequencer: P140,
P142, P441 = 27