Technical data, 600vac models – Lenze ESV SMV frequency inverter User Manual
Page 13

Lenze SMVector 13465100 EDBSV01 EN v18
11
Technical Data
600VAC Models
600V Three Phase (3/PE) (425...660V); 48...62Hz
Type
Power
Mains Current
Output Current
Heat Loss (Watts)
Hp
kW
A
Cont (I
n
)
A
Max I
%
N1/IP31
N4X/IP65
No filter
N4X/IP65
W/ filter
ESV751--6T--
1
0.75
2
1.7
200
37
31
ESV152--6T--
2
1.5
3.2
2.7
200
51
43
ESV222--6T--
3
2.2
4.4
3.9
200
68
57
ESV402--6T--
5
4
6.8
6.1
200
101
67
ESV552--6T--
7.5
5.5
10.2
9
200
148
116
ESV752--6T--
10
7.5
12.4
11
200
172
152
ESV113--6T--
15
11
19.7
17
180
380
356
ESV153--6T--
20
15
25
22
180
463
431
ESV183--6T--
25
18.5
31
27
180
560
519
ESV223--6T--
30
22
36
32
180
640
592
ESV303--6T--
40
30
47
41
180
930
ESV373--6T--
50
37.5
59
52
180
1163
ESV453--6T--
60
45
71
62
180
1395
NOTES:
Output Current: The Output Current Maximum (%) is a percentage of the Output Current Continuous Amps (In) rating
and is adjustable in parameter P171.
STOP!
• For installations above 1000m a.m.s.l., derate I
n
by 5% per 1000m, do not
exceed 4000m a.m.s.l.
• Operation above 40°C, derate I
n
by 2.5% per °C, do not exceed 55°C.
Output Current (In) derating for Carrier Frequency (P166) for NEMA 1 (IP31) Models:
- If P166=2 (8 kHz), derate I
n
to 92% of drive rating
- If P166=3 (10 kHz), derate I
n
to 84% of drive rating
Output Current (In) derating for Carrier Frequency (P166) for NEMA 4X (IP65) Models:
- If P166=1 (6 kHz), derate I
n
to 92% of drive rating
- If P166=2 (8 kHz), derate I
n
to 84% of drive rating
- If P166=3 (10 kHz), derate I
n
to 76% of drive rating