Commissioning, 6 network parameters – Lenze ESV SMV frequency inverter User Manual
Page 45

Lenze SMVector 13465100 EDBSV01 EN v18
43
Commissioning
4.5.6
Network Parameters
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p400
Network Protocol
0 Not Active
This parameter setting is based upon the network
or I/O module that is installed.
1 Remote Keypad
2 Modbus RTU
3 CANopen
4 DeviceNet
5 Ethernet
6 Profibus
7 Lecom-B
8 I/O Module
p401
Module Type Installed
0
0 No Module Installed
Module type format: 0xAABC; Drive Display:
AA.B.C
AA = Module Type
B = Major revision
C = minor revision
1 Basic I/O (0x0100, 1.0.0)
2 RS485/Rem. Keypad (0x0200, 2.0.0)
3 CANopen (0x0300, 3.0.0)
11 PROFIBUS (0x1100, 11.0.0)
12 Ethernet (0x1200, 12.0.0)
P402
Module Status
0
0 Not Initialized
1 Initialization: Module to EPM
2 Initialization: EPM to Module
3 Online
4 Failed Initialization Error
5 Time-out Error
6 Initialization Failed
Module type mismatch P401
7 Initialization Error
Protocol selection mismatch P400
P403
Module Reset
0
0 No Action
Returns module parameters 401…499 to the
default values shown in the manual
1 Reset parameters to default values
P404
Module Timeout Action
3
0 No Fault
Action to be taken in the event of a Module/
Drive Time-out.
Time is fixed at 200ms
STOP is by the method selected in P111.
1 STOP (see P111)
2 Quick Stop
3 Fault (F_ntF)
P405
Current Network Fault
0 No Fault
1 F.nF1
NetIdle Mode
2 F.nF2
Loss of Ethernet I/O connection
3 F.nF3
Network Fault
4 F.nF4
Explicit Message Timeout
5 F.nF5
Overall Network Timeout
6 F.nF6
Overall Explicit Timeout
7 F.nF7
Overall I/O Message Timeout
P406
Proprietary
Manufacturer specific
p407 … P499
Module Specific Parameters
Refer to the Communications Reference Guide
specific to the network or I/O module installed.