Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p207
Proportional Gain
5.0
0.0
{%} 1000.0
Used to tune the PID loop:
• Increase P207 until system becomes unstable,
then decrease P207 by 10-15%
• Next, increase P208 until feedback matches
setpoint
• If required, increase P209 to compensate for
sudden changes in feedback
p208
Integral Gain
0.0
0.0 {s} 20.0
p209
Derivative Gain
0.0
0.0 {s} 20.0
NOTE
•
Derivative Gain is very sensitive to noise on the feedback signal. Use with care.
•
Derivative Gain is not normally required in pump and fan applications
p210
PID Setpoint Ramp
20.0
0.0 {s} 100.0
• time of setpoint change from P204 to P205
or vice versa.
• Used to smooth the transition from one PID
setpoint to another, such as when using the
Preset PID Setpoints (P231...P233)
p214
Minimum Alarm
0.0
P204 P205
Use with P140, P142 = 18...23
P215
Maximum Alarm
0.0
P204 P205
P231
Preset PID Setpoint #1
0.0
P204 P205
TB-13A activated; P121 = 3 and P200 = 1 or 2
P232
Preset PID Setpoint #2
0.0
P204 P205
TB-13B activated; P122 = 3 and P200 = 1 or 2
P233
Preset PID Setpoint #3
0.0
P204 P205
TB-13C activated; P123 = 3 and P200 = 1 or 2
P234
(2)
Preset PID Setpoint #4
0.0
P204 P205
TB-13D activated; P124 = 3 and P200 = 1 or 2
P240
Sleep Threshold
0.0
0.0
{Hz} 500.0
• If drive speed < P240 for longer than P241,
output frequency = 0.0 Hz; drive display = SLP
• P240 = 0.0: Sleep mode is disabled.
• P200 = 0…2: Drive will start again when speed
command is above P240
• P242 > 0.0: Drive will restart when the PID
feedback differs from the setpoint by more
than the value of P242
or when the PID loop
requires a speed above P240.
P241
Sleep Delay
30.0
0.0 {s} 300.0
P242
Sleep Bandwidth
0.0
0.0 B
max
Where: B
max
= |(P205 - P204)|
P243
Feedback Sleep
Entry Threshold
0.0
P204 P205
Active only when P244 = 1 or 2
P244
Sleep Entry Mode
0
0 Enter SLEEP if Drive Speed For time longer than P241 1 Enter SLEEP if Feedback >P243 For time longer than P241 or same as Sel 0 2 Enter SLEEP if Feedback For time longer than P241 or same as Sel 0 P245 Sleep Entry Stop 0 0 Coast to Stop P246 Feedback Recovery 0.0 P204 P205 Active only when P247 = 1 or 2 P247 Sleep Recovery 0 0 Recovery if Speed Setpoint > P240 or if PID feedback differs from setpoint 1 Recovery only if Feedback < P246 (2) Parameter applicable to SMV models 15HP (11kW) and higher.
Type
1 Ramp to Stop
2 Stop with P111 settings
from Sleep Threshold
Mode
by more than P242
2 Recovery only if Feedback > P246