Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 39

Lenze SMVector 13465100 EDBSV01 EN v18
37
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p175
DC Brake Time
0.0
0.0 {s} 999.9
NOTE: CONFIRM MOTOR SUITABILITY FOR USE WITH DC BRAKING
DC Brake voltage (P174) is applied for the time specified by P175 with the following exceptions:
• If P111=1, 3 and P175=999.9 the brake voltage will be applied continuously until a run
or fault condition occurs.
• If P110=2, 4…6 and P175=999.9, brake voltage will be applied for 15s
• If P121…P124=18 and the corresponding TB-13 input is CLOSED, brake voltage will be
applied until the TB-13 input is OPENED or a fault condition occurs.
p176
Keypad Setpoint
Single Press
Increment
0.1
0.1 100.0
Used for run screen setpoint editing only.
If P176 >0.1 then scrolling of keypad setpoint
is enabled.
p177
(2)
Speed Units
0
0 Hz
Select the UNITS LED that will be illuminated when
the drive is running in speed control mode. For this
parameter to be used, P178 must be set to a value
other than 0. IF P178 is set to 0, the Hz LED will
be illuminated regardless of the value set in P177.
1 RPM
2 %
3 /UNITS
4 NONE
p178
Display Frequency
Multiplier
0.00
0.00 650.00
• Allows frequency display to be scaled
• P178 = 0.00: Scaling disabled
• P178 > 0.00: Display = Actual Frequency
X P178
EXAMPLE
If
P178 = 29.17 and actual frequency = 60 Hz, then Drive displays 1750 (rpm)
p179
Run Screen Display
0
0 {Parameter Number}
599
• 0 = Normal Run Screen, this display depends
on mode of operation. Refer to section 4.2.
• Other selections choose a diagnostic parameter
to display (P501…P599).
• Parameters P560 - P564 are selectable if
the sequencer is enabled (P700 is not 0).
P560-P564 are not visible until P700 is
enabled.
p180
Oscillation Damping
Control
0
0 80
0 = Damping disabled
Compensation for resonances within drive
p181
Skip frequency 1
0.0
0.0
{Hz}
500
• Drive will not run in the defined skip range;
used to skip over frequencies that cause
mechanical vibration
• P181 and P182 define the start of the skip
ranges
• P184 > 0 defines the bandwidth of both ranges.
p182
Skip frequency 2
0.0
0.0
{Hz}
500
p184
Skip frequency
bandwidth
0.0
0.0
{Hz}
10.0
NOTE
Bandwidth (Hz) = f
s
(Hz) + P184 (Hz) f
s
= P181 or P182
EXAMPLE: P181 = 18 Hz and P184 = 4 Hz; skip range is from 18 to 22 Hz
p185
Voltage Midpoint
V/Hz characteristic
0
0.0
{V}
P165
Valid only when P300 = 0 or 2.
Use with P187 to define midpoint on V/Hz curve.
p187
(2)
Frequency Midpoint
V/Hz characteristic
0.0
0.0
{Hz}
P167
Valid only when P300 = 0 or 2.
Use with P185 to define midpoint on V/Hz curve.
p189
(3)
Integrated Dynamic
Brake
0 Disabled
1 Enabled
(2)
Parameter applicable to SMV models 15HP (11kW) and higher.
(3)
Parameter applicable to SMV models 40HP (30kW) and higher.