Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 35

Lenze SMVector 13465100 EDBSV01 EN v18
33
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p140
Relay Output
TB-16, 17
0
0 None
Disables the output
1 Run
Energizes when the drive is running
2 Reverse
Energizes when reverse rotation is active
3 Fault
De-energizes when the drive trips, or power is
removed
4 Inverse Fault
Energizes when the drive trips
5 Fault Lockout
P110 = 3...6: De-energizes if all restart attempts
fail
6 At Speed
Energizes when output frequency = commanded
frequency
7 Above Preset Speed #6
Energizes when output frequency > P136
8 Current Limit
Energizes when motor current = P171
9 Follower Loss (4-20 mA)
Energizes when 4-20 mA signal is < P164
10 Loss of Load
Energizes when motor load drops below P145;
Refer to P146 also
11 Local Keypad Control Active
Energizes when the selected source is active for
start control
12 Terminal Strip Control Active
13 Remote Keypad Control Active
14 Network Control Active
15 Standard Reference Active
Energizes when P101 reference is active
16 Auto Reference Active
Energizes when Auto Reference is activated using
TB-13 input; refer to P121...P124
17 Sleep Mode Active
Refer to P240...P242
18 PID Feedback < Min. Alarm
Energizes when PID feedback signal < P214
19 Inverse PID Feedback < Min. Alarm De-energizes when PID feedback signal < P214
20 PID Feedback > Max Alarm
Energizes when PID feedback signal > P215
21 Inverse PID Feedback > Max Alarm De-energizes when PID feedback signal > P215
22 PID Feedback within
Min/Max Alarm range
Energizes when PID feedback signal is within the
Min/Max Alarm range; refer to P214, P215
23 PID Feedback outside
Min/Max Alarm range
Energizes when PID feedback signal is outside the
Min/Max Alarm range; refer to P214, P215
24 Reserved
25 Network Controlled
SMV models < 15HP (11kW) require an optional
communication module (refer to the network
module documentation).
26 Loss of 0-10V Input
Energizes when 0-10V signal is < P158
27 Sequencer Controlled
State set in individual sequencer segments
28 Sequencer Active
29 Sequencer Suspended
30 Sequence Done
End Sequence
31 Output Frequency = 0.0Hz
Output inactive
p142
TB-14 Output
0
0...23 (same as P140)
24 Dynamic Braking
For use with Dynamic Braking option
25...31 (same as P140)