Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 44

42
Lenze SMVector 13465100 EDBSV01 EN v18
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
p304
(1)
Motor Rated
Frequency
60
0
{Hz} 1000
Set to motor nameplate data
P305
(1)
Motor Rated Speed
1750
300
{RPM} 65000
P306
(1)
Motor Cosine Phi
0.80
0.40 0.99
NOTE If motor cosine phi is not known, use one of the following formulas:
cos phi = motor Watts / (motor efficiency X P302 X P303 X 1.732)
cos phi = cos [ sin
-1
(magnetizing current / motor current) ]
P310
(1)
Motor Stator
Resistance
0.00 {
W} 64.00
• P310, 311 default setting depends on drive rating
• Will be automatically programmed by P399
• Changing these settings can adversely affect
performance. Contact factory technical support
prior to changing
p311
(1)
Motor Stator
Inductance
0.0
{mH} 2000
P315
Dead Time
Compensation Factor
0.0
-50.0 {%} +50.0
• Adjust dead time correction from internal default
• Takes effect when P399 = 3.
P330
Torque Limit
100
0
{%} 400
When P300 = 5, sets the maximum output torque.
P331
Preset Torque
Setpoint #1
100
0
{%} 400
TB-13A activated; P121 = 3 and P300 = 5
P332
Preset Torque
Setpoint #2
100
0
{%} 400
TB-13B activated; P122 = 3 and P300 = 5
P333
Preset Torque
Setpoint #3
100
0
{%} 400
TB-13C activated; P123 = 3 and P300 = 5
P334
(2)
Preset Torque
Setpoint #4
100
0
{%} 400
TB-13D activated; P124 = 3 and P300 = 5
P340
(1)
Current Loop P Gain
0.25
0.00 16.0
Changing these settings can adversely affect
performance. Contact factory technical support
prior to changing.
P341
(1)
Current Loop I Gain
65
12
{ms} 9990
P342
(1)
Speed Loop Adjust
0.0
0.0
{%} 20.0
P343
Slip Compensation
Response Filter
99
90
{ms} 9999
Low pass filter time constant for varying the slip
compensation response to changes in the motor
current.
P399
Motor Auto-
calibration
0
0 Calibration Not Done
• If P300 = 4 or 5, motor calibration must be
performed if P399 is not set to 3 (bypass
calibration).
• If P300=2 or 3, motor calibration is
recommended.
• Use option 2 if option 1 failed or in case of non-
standard motors
• An alternating CAL / Err will occur if:
- attempt motor calibration with P300 = 0 or 1
- motor calibration is attempted before
programming motor data
1 Standard Calibration Enabled
2 Advanced Calibration Enabled
3 Bypass Calibration, enable
operation in vector mode w/o Auto
Calibration
4 Standard Calibration Complete
5 Advanced Calibration Complete
NOTE: To run the Auto Calibration:
− Set P302...P306 according to motor nameplate
− Set P399 = 1 or 2 (if option 1 failed or in case of non-standard motor)
− Make sure motor is cold (20° - 25° C)
− Apply a Start command
− Display will indicate CAL for about 40 seconds
− Once the calibration is complete, the display will indicate Stop; apply another
Start command to actually start the motor
− Parameter P399 will now be set to 4 or 5.
(1)
Any changes to this parameter will not take effect until the drive is stopped.
(2)
Parameter applicable to SMV models 15HP (11kW) and higher.