Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 32

30
Lenze SMVector 13465100 EDBSV01 EN v18
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P113
Auto/Manual Control
0
0 Terminal Strip Control
The reference is dictated by the settings and state
of the TB-13x terminals. If no AUTO reference has
been setup on the terminal strip then reference
control is dictated by P101.
1 Auto/Manual (CTRL button select)
Allows the reference to be switched between auto
and manual using the CTRL pushbutton on the
drive keypad. If the CTRL pushbutton has selected
AUTO reference but no AUTO reference has been
setup on the terminal strip, then reference control
is dictated by P101.
2 Manual Control Only
Reference is dictated by P101 regardless of any
AUTO source that may be selected by the TB-13x
terminals.
NOTE
P113 is applicable to SMV 15HP (11kW) and higher models only.
P115
MOP Speed
Initialization at
Power-Up
0
0 Set to last MOP speed at power up
Output frequency at power-up = last MOP speed
1 Set to 0.0Hz at power up
Output frequency at power-up = 0Hz
2 Set to Preset #3 (P133) at power up Output frequency at power-up = P133