Commissioning – Lenze ESV SMV frequency inverter User Manual
Page 38

36
Lenze SMVector 13465100 EDBSV01 EN v18
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
P164
TB-25 (4-20mA)
Analog Input
Monitoring Level
2.0
0.0
{mA} 20.0
P165
Base Voltage
15 {V} 1000
Valid for V/Hz mode only.
Set voltage for bus compensation in V/Hz mode
P166
Carrier Frequency
See
Notes
0 4 kHz
• As carrier frequency is increased, motor noise
is decreased
• Observe derating in section 2.3
• Automatic shift to 4 kHz at 120% load
• NEMA 4X (IP65) Models: Default = 0 (4kHz)
• NEMA 1 (IP31) Models: Default = 1 (6kHz)
1 6 kHz
2 8 kHz
3 10 kHz
p167
(1)
Base Frequency
60.0
10.0 {Hz} 1500
V0112
p168
Fixed Boost
0.0
{%} 40.0
NOTE
• P167 = rated motor frequency for standard applications
• P165, P168 = default setting depends on drive rating
p169
Accel Boost
0.0
0.0
{%} 20.0
Accel Boost is only active during acceleration
P170
Slip Compensation
0.0
0.0
{%} 40.0
Increase P170 until the motor speed no longer
changes between no load and full load conditions.
p171
(1)
Current Limit
Max I
30
{%}
Max I
• When the limit is reached, the drive displays
CL(Current Limit), and either the acceleration
time increases or the output frequency
decreases.
• Digital outputs can also indicate when the limit
is reached; see P140, P142.
• Refer to section 2.3 for the maximum output
current Max I (%)
P172
Current Limit
Reduction
0
0 Current Limit Reduction Active -
Normal response
In field weakening, the Current Limit is inversely
proportional to the speed.
1 Current Limit Reduction Active - Fast
response
2 Current Limit Reduction Disabled -
Normal response
3 Current Limit Reduction Disabled -
Fast response
P173
Decel Override Time
2.0
0.0 {s} 60.0
Maximum time before drive trips into HF fault.
P174
DC Brake Voltage
0.0
0.0
{%} 50.0
Setting is a percent of the nominal DC bus voltage.
(1)
Any changes to this parameter will not take effect until the drive is stopped.