Avaya 555-233-116 User Manual
Page 164

Stratum 3 clock
555-233-116
164
Issue 4 October 2002
2. Set the options on the Stratum 3 (ST3) clock board (see
).
NOTE:
Only SW 1 and SW2 are used. SW1 controls the output of alarm signals
from the Stratum 3 clock board.
3. Set the options on the composite clock timing output board (TOCA) per
4. Set the Stratum 2/Stratum 3 switch to the STRATUM 3 position.
NOTE:
Set switches 1 and 2 according to the distance from the Stratum 3 clock to
the DEFINITY system. Set switch 3 to ON. Set switch 4 to OFF.
Table 17.
ST3 clock board option switch settings
Switch
Status/Results
SW1
Minor alarm
control
OFF = minor alarm never output
ON = minor alarm is output if holdover occurs
SW2
Major Alarm
Control
OFF = major alarm is output and fail lamp lights if 5 VDC
power is lost and 4 kHz output is lost
ON = major alarm is output and fail lamp lights if 5 VDC
power is lost and 4 kHz output is lost and holdover occurs
Table 18.
Composite clock timing output board (TOCA)
Switch
Range in feet (meters)
500
1000
1.0
(0.3)
500
(152)
1000
(305)
1500
(457)
2000
(710)
2500
(772)
3000
(914)
OFF
OFF
ON
OFF
OFF
ON
ON
ON